Technical data 

Voltage (V DC) 

   rated 
   allowed 
   normal  

 

24 
12-30 
24 

Current consumption at nom. volt. 
(mA) 

   quiescent (detector only) 
   active (detector only) 

Depending on the base the detector is plugged into.  For more details see 
the Product Leaflet respectively, e.g. MEW00008 (Base 2324). 

0.04 
min. 3 

Ambient temperature (

°

C) 

  operating 
  storage 

 

-10 to +50 
-25 to +75 

Ambient humidity (% RH) 

max. 95, non condensing 

Ingress Protection rating (estimated) 

IP 51 

Sensitivity (obscuration; %/m) 

3.7 / 5 (depending on algorithm) 

 

>2.5 in combination with temp. rate-of-rise (depending on algorithm) 

Sensitivity (T=

°

C; 

deltaT=

°

C/min.

57; 

6.43 / not used

  (depending on algorithm) 

 

57; 

>1.07

 in combination with smoke obscur. (depending on algorithm) 

Size 

 x h (mm) 

102 x 46 

Weight (g) 

84 

Construction / Colour 

Modified polycarbonate / Grey (N8, Munsell colour code) 

Approvals 

 05  EC Certificate no. 0786-CPD-20143;   EN54-7 

 

A

The zone line is connected to the base 2324 (A-B) 