All technical features and data are subject to changes without notice, resulting from continuous development and improvement.
Product Leaflet
Date of issue
Revision / Date of revision
MEW00309 2002-12-03
5
/
2006-08-31
Type number
4350 Multi
detector
In the detector:
See also "Engineering Instructions for detectors Type 435x".
A
Contact for base 2324
B
Contact for base 2324
The detector is plugged in a base 2324.
Technical data
Voltage (V DC)
rated
allowed
normal
24
12-30
24
Current consumption at nom. volt.
(mA)
quiescent (detector only)
active (detector only)
Depending on the base the detector is plugged into. For more details see
the Product Leaflet respectively, e.g. MEW00008 (Base 2324).
0.04
min. 3
Ambient temperature (
°
C)
operating
storage
-10 to +50
-25 to +75
Ambient humidity (% RH)
max. 95, non condensing
Ingress Protection rating (estimated)
IP 51
Sensitivity (obscuration; %/m)
3.7 / 5 (depending on algorithm)
>2.5 in combination with temp. rate-of-rise (depending on algorithm)
Sensitivity (T=
°
C;
deltaT=
°
C/min.
)
57;
6.43 / not used
(depending on algorithm)
57;
>1.07
in combination with smoke obscur. (depending on algorithm)
Size
∅
x h (mm)
102 x 46
Weight (g)
84
Construction / Colour
Modified polycarbonate / Grey (N8, Munsell colour code)
Approvals
05 EC Certificate no. 0786-CPD-20143; EN54-7
A
B
The zone line is connected to the base 2324 (A-B)
Ext. LED is connected to the base 2324 (A-L).