38
004778290 - 21/01/2021
3.1.4 "Eco mode” function
Function available in configurations 2, 3 and 4
only (
*
).
By enabling this function, the device is turned off
when the desired room temperature is reached.
If this function is not enabled, the device modu-
lates its operation without shutting down.
To activate/deactivate this function:
Eco mode
Eco mode
Restart temp.
1,2
Fig. 20
“Eco mode” function inactive
“Eco mode” function active
When the “Eco mode” function is activated, the
“Restart temp.” option becomes available, which
is the number of degrees below the set tempera-
ture after which the device automatically restarts.
Eco mode
Eco mode
Restart temp.
1,2
Fig. 21
Example
: if the device is set to shut down at 20°C
(“Eco mode” function active) and we set a "Re-
start temp." of 4°C, the device will turn on again
when it detects a temperature less than or equal
to 16°C.
The values can be set from 0.5 ... 5.0 °C.
(*) In configuration 3 and 4, it is not possible to
activate or deactivate the function, but it is
only possible to set the “Restart temp.”.
3.1.5 "Antifreeze" function
Function available in configurations 2, 3 and 4
only.
A minimum temperature can be set below which
the device will switch on (outside the set time
bands and only if the timer is enabled).
To modify the "antifreeze" temperature value:
Antifreeze
OFF
OK
Fig. 22
Antifreeze
16
OK
Fig. 23
Settable values:
(OFF; 3 ... 20°C) for configuration 2
(OFF; 3 ... 50°C) for configurations 3 and 4