background image

Installation and Test

 363-704-104-01, Revision 01

10

June 22, 1998

 FLC-704 List 4

Troubleshooting

Table 10

 provides troubleshooting procedures based on indications displayed by the front panel indicators of the

FLC-704 List 4 channel unit.

Table 10.

FLC-704 List 4 Channel Unit Troubleshooting

Indication

Problem

Action

FAULT LED 
ON

The FLC-704 processor 
has detected a fault.

Remove and reinsert the Channel Unit. If the FAULT LED does not extinguish, replace the 
Channel Unit.

Troubleshooting based on customer-originated trouble reports

No Dial tone, 
Can’t Dial

faulty RT or COT 
Channel Unit

facility short/open

CO switch problem

Tip/Ring reversed at 
CO

1

Lift the subscriber pair at the network interface. If dial tone is present and you can place 
a call, refer the problem to the customer per local practice.

2

If you cannot hear a dial tone or cannot place a call at the network interface (with the 
subscriber pair lifted), check for dial tone at the RT. If a dial tone is present, check the 
pair between the RT and the network interface. If no dial tone is present, replace the RT 
Channel Unit.

3

If the problem still exists, re-insert the original RT Channel Unit and replace the COT 
Channel Unit. Test for operation.

4

If the problem still exists, refer the problem to the CO switch.

Phone 
Doesn’t Ring

high-resistance 
subscriber line short

faulty RT or CO 
Channel Unit

loop length too long

1

Lift the subscriber pair at the network interface. If ringing is present, refer the problem 
to the customer per local practice.

2

If ringing is not present, check for ringing at the RT. If ringing is present, check the pair 
between the RT and the network interface. If no ringing is present, replace the RT 
Channel Unit. If ringing is still not present, check a circuit on another Channel Unit. If 
ringing is still not present, replace the Line Unit.

3

If ringing is still not present at the RT, re-insert the original Channel Unit and Line Unit. 
Test for ringing at the COT.

4

Test for ringing into the COT from the CO switch. If no ringing is present, refer the 
trouble to the CO switch. If ringing is present, replace the COT Channel Unit. Test again 
for ringing at the network interface. If ringing is still not present, contact PairGain 
technical assistance per 

“Product Support” on page 11

.

5

Verify the resistance of the copper loop between the RT Enclosure and the network 
interface is less than 530 

.

Phone 
doesn’t stop 
ringing

faulty subscriber 
instrument

faulty RT Channel 
Unit

loop length too long

1

Test for ring trip at the network interface. If the ringing is tripped, refer the trouble to 
the customer per local practice.

2

If the ringing is not tripped, test for tripping at the RT. If ring trip does occur, check the 
loop for excessive length. If ring trip does not occur, replace the RT Channel Unit. If 
ring trip still does not occur, contact PairGain technical assistance per 

“Product 

Support” on page 11

.

3

Verify the resistance of the copper loop between the RT Enclosure and the network 
interface is less than 530 

.

Can’t Hear, 
Can’t Be 
Heard

subscriber problem

faulty RT or COT 
Channel Unit

1

Lift the subscriber line at the network interface and check the signal level. If correct, 
refer trouble to the customer per local practice.

2

If the level is too low, check the level at the RT. If the level is correct at the RT, check 
the pair between the RT and the network interface. If the level is too low at the RT, 
replace the RT Channel Unit.

3

If the level is still too low, re-insert the original RT Channel Unit.

4

Check the level at the COT coming from the CO switch. If it is correct, replace the COT 
Channel Unit. If it is not correct, refer the problem to the CO regarding the switch.

5

If the level is still not correct, re-insert the original COT Channel Unit. Contact PairGain 
technical assistance per 

“Product Support” on page 11

.

Summary of Contents for PG-Flex FLC-704

Page 1: ...L CENTRAL OFFICE TERMINAL LOOP START GROUND START POTS UNIT PAIRGAIN TECHNOLOGIES INC ENGINEERING SERVICES TECHNICAL PRACTICE 363 704 104 01 SECTION 363 704 104 01 Model List Number Part Number FLC 70...

Page 2: ...n contained in this document is company private to PairGain Technologies Inc and shall not be modified used copied reproduced or disclosed in whole or in part without the written consent of PairGain O...

Page 3: ...4 List 4 June 22 1998 iii USING THIS TECHNICAL PRACTICE Two types of messages identified by icons appear in the text Notes contain information about special circumstances Cautions indicate the possibi...

Page 4: ...rt Operation 4 Ground Start Operation 6 CLASS Features 7 Forward Disconnect 7 Installation and Test ___________________________________________________________________ 8 Unpacking 8 Installing 8 Provi...

Page 5: ...subscriber line connection through an optional metallic bypass pair for subscriber circuit testing Features of the PG Flex FLC 704 List 4 COT channel unit are eight loop start or ground start POTS sub...

Page 6: ...Fast flashing green Channel is in test access mode Slow flashing green LED follows the ring signal Off Channel is on hook idle FAULT Red Fault detected by the unit Refer to Table 10 on page 10 for tr...

Page 7: ...100 Hz Ring Ground Resistance 500 Channel Signature Loop Start Lines Ground Start Lines Tip Ring open 23 75k 1 Tip Ground 162k 1 162k 1 Ring Ground 226k 1 226k 1 Environmental Operating Elevation 200...

Page 8: ...ing or under test see Table 1 on page 2 for front panel LED definitions Loop Start Operation The following section summarizes the loop start sequences for on hook idle subscriber inititated outgoing c...

Page 9: ...t interactions Table 3 Circuit Interactions When a Subscriber Initiates an Outgoing Call Loop Start Operation CO Switch FLC 704 List 4 COCU FRL 754 List 4 RTCU Subscriber CO Idle No ringing No ringing...

Page 10: ...tgoing calls may occur simultaneously on the same line Glare occurs when both ends of a telephone line or trunk are seized at the same time CO sends dial tone and grounds the Tip to signal the PBX to...

Page 11: ...ated the CO generates analog signalling toward the PBX between the first and second bursts of the ringing signal Forward Disconnect The forward disconnect function releases a called line that was left...

Page 12: ...he equipment in its original container Installing 1 Insert each FLC 704 Channel Unit into the COT shelf and observe that all LEDs turn ON for approximately 2 seconds scan from top to bottom flash all...

Page 13: ...f the call refer to Table 1 on page 2 for front panel indications Place an incoming call to each subscriber circuit provisioned and verify that the ACTIVE LED tracks the progress of the call refer to...

Page 14: ...ent replace the Line Unit 3 If ringing is still not present at the RT re insert the original Channel Unit and Line Unit Test for ringing at the COT 4 Test for ringing into the COT from the CO switch I...

Page 15: ...mission speeds up to 28 8 kbps are supported with a character format of 8 N 1 Warranty PairGain Technologies warrants this product to be free of defects and to be fully functional for a period of 60 m...

Page 16: ...o radio communications Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense...

Page 17: ...ng Services CO Central Office COT Central Office Terminal DS0 Digital Signal Level Zero 64 kb s DTMF Dual Tone Multi Frequency HDSL High bit rate Digital Subscriber Line kbps KiloBits Per Second MLT M...

Page 18: ......

Page 19: ......

Page 20: ...Corporate Office 14402 Franklin Avenue Tustin CA 92780 Tel 714 832 9922 Fax 714 832 9924 For Technical Assistance 800 638 0031...

Reviews: