pH/chlorine regulator AUTODOS 5000 - 2005-01-21
Eng_Autodos5000.doc ver 3.2 - page 34
Channel Specific Set-up (Combined Chlorine):
Row
Text
Setting
Explanation
-01
dos
ono
Dosing type – on-off
-02
P
0.20
P-band
-03
d
000
D-time
-04
dF
100
Max. dosing frequency, strokes/min
-05
Ldt
000 (min)
Long dosing time alarm, (no alarm function)
-06
oFt
000 (sec)
Min. time OFF for relay, (no function (on-off))
-07
ont
000 (sec)
Min. time ON for relay, (no function (on-off))
-08
Cur
--4
Current output 4-20mA
-09
C-L
0.00
Value for 4mA
-10
C-H
5.00
Value for 20mA
Channel Specific Set-up (pH - Acid/Alkali):
Row
Text
Setting
Explanation
-01
dos
ono
Dosing type – on-off
-02
P
0.20
P-band
-03
d
000
D-time
-04
dF
100
Max. dosing frequency, strokes/min
-05
Ldt
000 (min)
Long dosing time alarm, (no alarm function)
-06
oFt
000 (sec)
Min. time OFF for relay, (no function (on-off))
-07
ont
000 (sec)
Min. time ON for relay, (no function (on-off))
-08
Cur
--4
Current output 4-20mA
-09
C-L
6.00
Value for 4mA
-10
C-H
8.50
Value for 20mA