The chimney may incorpo-
rate an offset. To do this
safely, all sections of listed
connector, offset elbows
and chimney section must
be screwed together by
at least three sheet metal
screws per joint. The
chimney must be suitably
supported by the chimney
manufacturer's listed offset
support.
Procedure
1. Position stove and floor protection with hole for combustion air in accordance with the clearances as stated on the
label and in Figure 16.
2. Mark the position for the hole in the ceiling and roof by using a string and plumb-bob.
3. Check that the intended location will not interfere with floor joists, ceiling joists or rafters before proceeding further.
4. Cut a hole in the ceiling and roof to suit the chimney system and frame in the sides. The chimney support is mounted
to the framing.
5. Install all components to the chimney manufacturer's installation requirements. (Outside combustion air may be
required, consult local building codes. See "Combustion Air" on page 19).
Unit may be harder to start.
Please provide as much
vertical length for the first
section of pipe as possible.
*
Combustible Wall/Ceiling Installation
Chimney
Storm collar
Spark arrestor
Rain cap
Radiation shield
3' (914 mm)
Minimum
Roof
flashing
Chimney
Support
Wall
Thimble
Alternate
up and out
installation
12"(305mm) minimum
Minimum 7' (2.1m.)
Ceiling height from
bottom of legs
*
12"(305mm)
Minimum first
section of pipe
Chimney
connector
Non-combustible
floor protector
Hooded vent or
90° elbow turned
down
Attachments to floor
for mobile homes
3” diameter air inlet with rodent screen.
If the crawl space is well ventilated it is
not necessary to extend air inlet to outside
48”
(1.2 m)
*
*
Figure 16: Alt 1.2 Combustible wall installation diagram.
210618-28_ALT 1.2
16
5055.7298-A