INSTALLATION AND OPERATION MANUAL
PAC HEAT RECOVERY WATER HEATER
Page
19
INSTALLMENT
PAC Heat Recovery Water Heater PAS model can be installed inside and outside
building. For installation should be check for capability of PAC tank PAS model because
it is an important point for investigation. The weight is showing on Table 1.
PAC Heat Recovery Water Heater PAS model should be located as near as
practical to the refrigeration unit. Careful planning of the Pac tank location and plumbing
can reduce installation costs and save time during installation and on maintenance in the
future.
1.
Installations Location
1.1 In case of installed multi air condition need to choose the most frequently
used air and need to choose the size that most BTU.
1.2 Choose a location to install the machine near the condensing unit as much as
possible by taking into account the length of the tube-term solution that does not exceed
more than 8 meters, use the solution pipe as the same size as a solution pipe which out
from the compressor.
Should be extened pipe solution if you need to pipe more than 8 meters. If you have
any question, please contact manufacturer.
In normally the total length of solution pipe should not exceed more than 16 meters.
X
< 8 m.