background image

8

being opened and closed depending on the room thermostat input. Additionally, mixing

valve is opened in case of overheating or boiler temperature sensor malfunction.

[Ar 3] mode

– output may control boiler emergency cooling system (e.g. pump). In this

mode the additional output is turned on in case of boiler overheating or boiler

temperature sensor error alarm.

[Ar 4] mode

– output may control devices working together with blow-in fan.

CAUTION.

Equipment should be connected to additional output using UM-1module.

Connection schemes are shown on picture 3.

4.7. Testing of device's outputs.

To make checking the controller work easier, it is possible to test output circuits which

control the fan and the pump, and the circuit which controls additional boiler. This

function is available in service mode, only if the control process is off, i.e. the controller

was in STOP mode before switching to service mode. By choosing

[outP]

on the

display and pressing OK button you can turn on the circulating pump for a while, by

choosing

[outΠ]

and pressing OK you can turn on the pressure fan and by choosing

[outr]

and pressing OK you can turn the additional boiler, the alarm signaling system

or the mixing valve servo-motor on (if the additional module is connected).

4.8. Factory defaults.

You can return to standard settings, set by the producer, by choosing

[Prod]

option in

service mode and pressing OK button. After activating this function, the device sets

each parameter showed in the table to default.

4.9. Exiting service mode.

By choosing

[End ]

option on the display and pressing OK button you can quit service

mode. The device also quits service mode, when no buttons are pressed for 1 minute.

5. Additional functions.

In order to improve comfort in heated rooms the controller is equipped with indoor

temperature sensor connection. RK-2001E2D compares measured room temperature

with value set with room thermostat knob. When the temperature is lower than desired

temperature circulation pump is turned on and room thermostat indicator is lit, which

means that boiler should keep temperature set with boiler thermostat knob. When

desired room temperature is reached circulation pump and indicator are turned off and

the boiler enters fire keeping mode and works at minimal temperature.

Design of the controller allows connecting any contact thermostat in place of indoor

temperature sensor. Shorting of this thermostat contacts when room temperature is

low will start heating procedure described earlier. When contacts aren't shorted the

controller keeps minimal boiler temperature.

Warning!

When contact thermostat is connected in place of indoor temperature

sensor, the value set with controller room thermostat knob won't affect the controller

operation, and room temperature will depend only on value set on contact thermostat.

Summary of Contents for RK-2001E2-D

Page 1: ...OPERATION MANUAL SOLID FUEL FIRED BOILER TEMPERATURE CONTROLLER RK 2001E2 D Version 9A15...

Page 2: ......

Page 3: ...placed in measurement hole in the boiler Picture 2 shows diagram of electrical connection of the device WARNING Before plugging the device to the power source check if it is proprerly grounded and if...

Page 4: ...ler If the controller isn t in service mode the display shows water temperature of the boiler and the last sign on the display defines mode which controller currently is in for example 50 STOP mode 50...

Page 5: ...olling emergency cooling system 4 output controlling extra devices turning on during work of blow in fan 0 4 1 0 Prod Return to factory defaults outP Central heating pump testing outP out1 out Fan out...

Page 6: ...in the boiler which causes start of the circulating pump Circulating pump works independently from the control process and is launched additionally in case of boiler overheat Circulating pump launch...

Page 7: ...o previous mode by pressing STOP button No fuel testing time during fuel firing is finished after the set temperature is achieved No fuel testing time during work mode Fb30 in WORK mode if temperature...

Page 8: ...set by the producer by choosing Prod option in service mode and pressing OK button After activating this function the device sets each parameter showed in the table to default 4 9 Exiting service mode...

Page 9: ...d if boiler overheats E 3 error means fault and overheating at the same time Appearing of E 1 error on the display without ability to cancel it by pressing STOP button in spite of temperature below 90...

Page 10: ...10 Picture 2 RK 2001E2 connection scheme Picture 3 UM 1 module connection scheme...

Page 11: ...2 The work mode and pause time of CH pump L 65 Minimum boiler temperature H 85 Maximum boiler temperature h 2 Boiler temperature hysteresis A 99 Boiler overheating temperature Fd60 Fuel shortage testi...

Page 12: ...12...

Page 13: ...13...

Page 14: ...14...

Page 15: ......

Page 16: ...Producer P W KEY 11 200 Bartoszyce ul Bohater w Warszawy 67 tel 89 763 50 50 fax 89 763 50 51 www pwkey pl e mail pwkey onet pl...

Reviews: