6.2 Trouble Shooting and Repair Guide
( Refer all repair work to qualified technical service personnel! )
6.3 Motor Driver Adjustments
CURRENT ADJUSTMENT PROCEDURE:
The motor driver board has an overcurrent protection feature with adjustable threshold by RV1.
1.
Do not change speed setting unless a replacement board is installed. Otherwise, set the speed at factory default .
2.
Adjust ‘current’ carefully by observing red ‘overcurrent’ LED. The LED should blink for minimal duration each time the motor
starts. If the led blinks too long and brightly, turn adjustment left (CCW) for minimal flash duration.
Note:
If the speed setting is changed, ‘current’ must be re-adjusted.
Caution!
Panel may stall and retreat with no obstacle if RV1 setting is too low. In this case turn RV1 counter clockwise to reduce sensitivity.
If the setting is too high then panel may exert excessive pressure on an obstacle.
Description of Fault
Possible Cause
Recommended Action
No power. (indicators, buzzer
off)
1. No AC power supplied to unit.
2. Loose power cable
3. Blown fuse
4.
Faulty power supply unit
1.Restore AC power.
2. Connect power cable.
3. Replace fuse (see 2.2)
4. Replace power supply unit
Turnsile does not allow
passage when input contact
is given-buzzer heard,
indicator turns green
1. Restricted panel movement (due to
foreign object blocking movement)
2. Motor driver circuit breaker tripped
3. Loose motor connection
4. Blown motor driver fuse
5.
.
1.Remove object
2. Power off reset
3. Repair connection
4. Replace motor driver board fuse
Panel oscillates right and left
in the middle position
1. Misaligned/ bent photosensor
Adjust photosensor (reduce angle)
No response to input/reader
Turnstile remains open with
alarm sound.
device. No access
1. Loose/incorrect reader connection
2-Reader fault
1. Emergency (Emg) input jumper removed.
2.Fire alarm relay connection fault.
1. Connect jumper on Emg-Gnd terminals
2.Repair fire alarm (NC)connection
3-Faulty control board
1.Check/repair reader connections
3-Replace faulty reader/input device
4-Replace control board
Motorized rotor/ panel keeps
moving/ fails to stop in
middle position.
1. Loose photosensor connector
2. Misaligned, bent or contaminated
photosensor
3. Faulty photosensor
1. Repair/tighten photosensor connector
2. Adjust/ clean photosensor
3. Replace photosensor
Motorized panel opens
slowly and times out on
return/ alarm activated.
1. Too low motor speed setting on motor
driver board
1. Increase motor speed (turm speed control ccw
direction) on motor driver board
Speed Adj.
Overcurrent LED
Current Adj.
5.
Electronic circuit protection activated
Power off reset