2

SYMBOLS USED

Warning of a potential danger, comply with Operator’s manual.

Caution! Dangerous voltage. Danger of electric shock. 

Double insulation. 

Suitable for live working. 

Conforms to European Union Directives. 

Measurement Category III is applicable to test and measuring circuits connected to the 

distribution part of the building’s low- voltage MAINS installation.

Measurement Category IV is applicable to test and measuring circuits connected at the 

source of the building’s low-voltage MAINS installation.

SAFETY INFORMATION

• Reference. Please use utmost attention.
• Do not exceed the maximum allowable input range of any function
• Insulated personnel body protective equipment up to 1000V.
• Unauthorised persons are not to be allowed to disassemble the Voltage Tester.

In order to avoid electrical shock, the valid safety and VDE regulations regarding excessive 

contact voltages must receive utmost attention, when working with voltages exceeding 

120V (60V) DC or 50V (25V) rms AC. The values in brackets are valid for limited ranges (as 

for example medicine and agriculture).
Prior to measurement ensure that the test leads and the Voltage Tester are in perfect condition. 
When using this instrument keep fingers behind the finger guards on the probes  

and do not touch the probe tips. 
This instrument may only be used within the ranges specified and within low voltage 

systems up to 1000V. 
Prior to usage, ensure that the Voltage Tester is fully working (e.g. on known voltage source). 
The Voltage Tester is not to be used, if the battery compartment is open.
The Voltage Tester must be kept dry and clean. 
The Voltage Tester may no longer be used if one or several functions fail or if no 

functionality is indicated.
Do not use in damp conditions. 
A Perfect display is only guaranteed within a temperature range of -10°C up to +55°C,  

at relative humidity of <85%.
If the operator’s safety cannot be guaranteed, the instrument must be removed from service 

and protected against use.

Summary of Contents for OXD-516-8260F

Page 1: ...CZ HU PL SK TH cromwell co uk Voltage test up to 1000V AC DC Single pole phase test Continuity test Rotary field indication Polarity indication Hold function CAT III 1000V CAT IV 600V LCD backlight C...

Page 2: ...t receive utmost attention when working with voltages exceeding 120V 60V DC or 50V 25V rms AC The values in brackets are valid for limited ranges as for example medicine and agriculture Prior to measu...

Page 3: ...learly indicate the absence of operating voltage in case of presence of interference voltage When the indication voltage present appears on a part that is expected to be disconnected of the installati...

Page 4: ...atic Polarity detection Full range Internal basic load impedance peak current Maximum 3 5mA at 690V 200k Is 3 5 mA no RCD tripping Operation time Duration Time 30 seconds Recovery time Recovery Time 2...

Page 5: ...er4 mm screw on BEFORE USING THE VOLTAGE TESTER Ensure that the Voltage Tester is in perfect condition For example keep an eye out for a broken housing or leaking batteries Before using at locations w...

Page 6: ...elete the recorded value press the HOLD button once again The LCD and LEDs display once again indicates the voltage currently being applied to the probe tips SINGLE POLE PHASE TEST The single pole pha...

Page 7: ...e battery power the Voltage Tester will automatically turn off after 4 minutes MEASUREMENT POINT ILLUMINATION The Voltage Tester is equipped with a measurement point illumination feature Press the but...

Page 8: ...s that have reached the end of their life must be collected separately and returned to an environmentally compatible recycling facility Do not dispose of electrical goods with domestic waste materials...

Reviews: