31
Unibox TQ RTL Installation
102273980-V01.06.2019
Mechanical
influences
Protected from mechani-
cal agitation
Radiation
Protected from UV rays
and direct sunlight
Chemical
influences
Do not store together
with solvents, chemicals,
acids, fuels or similar
substances
6. Installation
6.1 General installation advice
Note the following prior to installation:
• The lower edge of the “Unibox TQ RTL”
must be at least 20 cm above the finished
floor.
• The front edge of the “Unibox TQ RTL”
must be level with the finished wall.
Should the wall not have been
finished, take the plaster and tile
thickness into account.
• The opening of the wall box unit must face
downwards.
•
The thermostat must not be influenced by
other heat sources.
•
Use the enclosed brackets to align and fix
the “Unibox TQ RTL”.
NOTICE
Risk of damage due to lubri-
cants!
Seals may be destroyed by greasing
agents or oil.
f
Do not use any greasing agents or
oil for the installation.
f
Flush any dirt particles or grease
or oil residues out of the pipework
before installing the product.
f
When selecting the operating fluid,
please take the latest develop-
ments in technology into account
(e.g. VDI 2035).
1
2
3
4
5
6
7
Illustr. 8: Installation cross section
(1)
Masonry
(2)
“Unibox TQ RTL”
(3)
Plaster
(4)
Pipe conduit unit (separate accessory)
(5)
Edge insulating strip (separate acces-
sory)
(6)
Screed
(7)
Protective tube (separate accessory)