Valves, co systems

“Regusol” DN 25

Transmission station with controller

Technical advice

Important  information  on  the  replacement/con-
nection of controllers and speed controlled high-
efficiency pumps

In addition to the power supply cable (230 V), speed
controlled  high-efficiency  pumps  call  for  a  separate
cable  for  the  transmission  of  the  control  signal.  The
most common control signals are 0-10 V and pulse-
width  modulated  signals  (PWM)  of  proportional  and
inverted type.

The  type  of  signal  is  specified  in  the  operating  in-
structions  of  the  corresponding  pump!  If  the  control
signals of the controller and the pump are not coordi-
nated, an operation is not possible.

To avoid malfunctions and severe damage to installa-
tions  with  speed  controlled  high-efficiency  pumps,
the following must be observed:

– The pump must only be replaced with a pump with

identical control signal!

– The controller must only be replaced with a controller

with identical control signal!

– When combining a pump and a controller with dif-

ferent control signals, operating safety is no longer
guaranteed. Wrong control signals may cause da-
mage to the installation and endanger health!

– The following functional test has to be carried out

when putting the controller or pump into operation
and when replacing them:

– Switch  pump  to  “ON”  in  the  manual  menu  (relay

test) – the pump is in operation now.

– Now switch pump to “OFF” in the manual menu –

the pump is no longer in operation.

– Work on electrical installations must only be carried

out by a qualified electrician.

– Always disconnect the power supply before starting

work on electrical components.

– If not stated otherwise, all work and settings must

only be carried out by a trained tradesman.

– Under  working  conditions,  high-efficiency  pumps

are almost silent. Malfunctions caused by airlocks
could be confounded with a pump defect. This has
to  be  taken  into  account  when  carrying  out  the
functional test!

The installation and operating instructions that come
with the pump, controller and station have to be read
in their entirety before installation and initial operation.
The  instructions  have  to  remain  with  the  user  of  the
system. 

Claims  of  any  kind  due  to  damages  caused  by  the
nonobservance  of  the  instructions  or  incorrect  use
cannot be accepted.

General information regarding pin assignment:

Control line

Power supply 230V

blue

L
N

PE

brown

GND 

(earth

)

Signal output
(PWM or 0-10 V)

EN