Commissioning
Thermostatic valve AQH
28
118309480-V01.05.2020
Presetting values,
∆p = 150 mbar - 1500 mbar
∆t = 20 K
Presetting
qm [kg/h]
V
[l/s]
Heat output
0.5
50
0.0139
1200 W
1.0
100
0.0278
2300 W
1.5
150
0.0417
3500 W
2.0
200
0.0556
4650 W
2.5
250
0.0694
5800 W
3.0
300
0.0833
7000 W
3.5
350
0.0972
8150 W
4.0
400
0.1111
9300 W
4.2
420
0.1167
9800 W
7.2
Differential pressure measurement
To find out whether the differential pressure is high enough for an automatic
flow control of the thermostatic valve AQH, you measure the differential
pressure with the help of the Oventrop measuring system OV-DMC 3, the
differential pressure measuring stem and the Demo-Bloc (see section 4 auf
Seite 23).
Proceed as follows:
1. Unscrew the valve insert with the help of the Demo-Bloc.
For further information please refer to the operating instructions
supplied with the Demo-Bloc.
2. Measure the differential pressure with the help of the differential pres-
sure measuring stem. The differential pressure must reach or exceed the
differential pressure Δp min. (see section 3.3 auf Seite 22).
3.
Refit the valve insert. The torque amounts to 15 Nm.
4. Carry out a leakage test.