6.1  Status LED

1

Illust. 6:  Status LED

(1)

Status LED

The status LED is located under the casing cover 
and displays the operating status of the actuator.

Status-LED

Bedeutung

Flashing red

Charging of the capacitors after 

switching on

Flashing green

Initialisation run, recognition of neut-
ral point active

Lit green

Operating voltage applied, normal 
operation

Off

Emergency control mode triggered, 
no operating voltage

6.2  Normal operation

The actuator is automatically controlled via the con-
trol technology.

6.3  Emergency control function

 

Z

If the operating voltage fails, the actuator will move 

to the set emergency end position.

 

Z

Once the operating voltage has been restored, the 

energy store will be charged first.

 

Z

After that, the actuator will follow the signals of the 

control technology.

The emergency control function will only be 

available after successful completion of the 

initialisation run (displayed by a constantly lit 

green LED ).

7.  Maintenance

The actuator is maintenance-free.

8.  Removal and reinstallation

8.1  Removal

1

Illust. 7:  Stroke position indicator

(1)

Stroke position indicator of the actuator

CAUTION

Risk of burns due to hot components

An unprotected contact with hot components 

may lead to burns.

 

f

Allow the valve to cool down before work

-

ing on it.

NOTICE

It may not be possible to unscrew the 

collar nut by hand

Without operating voltage, the actuator may 

close the valve with the maximum actuating 
power of 200 N. In this case, the collar nut 
can no longer be unscrewed by hand.

 

f

Do not use pliers or similar to loosen the 

collar nut!

1. 

Set the DIP switch 6 to "ON" (see section 

5.2 on 

page 9).

2. 

Disconnect the actuator from the power supply.

 

Z

The actuator will move to the upper stroke position.

3.  Disconnect all electrical connections.
4.  Loosen the collar nut.
5.  Remove the actuator from the valve.

Summary of Contents for Aktor M ST L

Page 1: ...Valves controls systems Operating instructions EN Electromotive actuator Aktor M ST L 24 V 0 10 V...

Page 2: ......

Page 3: ...isk of burns due to hot components and surfaces 6 2 3 3 Availability of the operating instructions 6 3 Technical description 7 3 1 Construction 7 3 2 Functional description 7 3 2 1 Normal operation 7...

Page 4: ...Contents Aktor M ST L 24V 4 101271784 V02 01 2020...

Page 5: ...s located on the bottom of the prod uct 1 3 Extent of supply Items included in the delivery Aktor M ST L 24 V modulating proportional actuator 0 10 V Operating instructions 1 4 Contact OVENTROP GmbH C...

Page 6: ...to death or seri ous injury if not avoided CAUTION Indicates a possible danger with low risk It may lead to minor and reversible injury if the situation is not avoided NOTICE Indicates a situation wh...

Page 7: ...oning 6 8 VA 24 V AC 3 3 W 24 V DC nominal 5 3 VA 24 V AC 2 7 W 24 V DC Start up load For short periods max 12 A Drive Steady control 0 10 V DC 0 5 mA Connection Fixed pre assembled cable 1 5 m 5 x 0...

Page 8: ...or the installation of the actuator when installing the valve The actuator must only be connected to the power supply after installation CAUTION Risk of burns due to hot components An unprotected cont...

Page 9: ...stem may be damaged by exceeding the defined range of extension f Only operate the product in mounted state After having connected the power supply the internal energy store will be charged first befo...

Page 10: ...trol technology The emergency control function will only be available after successful completion of the initialisation run displayed by a constantly lit green LED 7 Maintenance The actuator is mainte...

Page 11: ...ntal pollution Incorrect disposal for instance with the domestic waste may lead to environmental damage f Packaging material is to be disposed of in an environmentally friendly manner f Components are...

Page 12: ...ON ON 2101 2500 l h OFF ON OFF OFF ON ON ON OFF ON ON DN 32 600 4800 l h 600 800 l h ON ON OFF OFF ON 801 2800 l h OFF OFF ON OFF ON OFF ON ON ON ON 2801 4800 l h ON OFF ON OFF ON ON ON ON ON ON Coco...

Page 13: ......

Page 14: ...OVENTROP GmbH Co KG Paul Oventrop Stra e 1 59939 Olsberg GERMANY www oventrop com 101271784 V02 01 2020...

Reviews: