- 4 - 

 

 

 

 

Commissioning Steps 
 
 

 

1. Testing for proper actuating device installation and testing the electrical connection 

 

 

 

 

 

 
2. Adjusting the valve functions 

 

 

The valve function is adjusted using the 4 switches beneath the emergency 

 

 

actuator hood. 

 

 

 

 

 

 

 

(1) 

Switch:

 

Switch on/switch off 

 

Factory setting: 

0 (Aus) 

 

 

valve block protection 

 
 

 

(2) 

Switch:

 

Setting of the control 

 

Factory setting:

 0-10V 

 

 

range of the actuating signal   

 

0-20mA 

 

 

 

 

 

 

 

 

  

 

(3) 

Switch:

 

Setting of the actuating 

 

Factory setting

: V

 

 

 

signal Y and position feedback 

 

 

live or energized 

 
 

 

Feedback when the valve is blocked or during manual adjustment is 

 

 

-energized feedback signal > approx. 12.5 V 

 

 

-live feedback signal 0 mA (with 4–20 mA) 

 
 

 

 
(4) 

Switch: 

Sequence setting for controlling 

Factory setting:  

 

 

the actuating direction 

 

 

“valve open” or “valve closed” 

 

 

(e.g. DC 0–10 V or DC 10–0V) 

 

 

  

Position feedback 

 

 

Note 
Inverting the control signal (          ,           ) also adjusts the sequence of the position feedback. The control signal and 
the actuating feedback are coupled to each other in their sequence. 
______________________________________________________________________________________________ 

 
3. Switch on the power supply 

 

 

LED (2) flashes. 

 
 
 

 

4. Initialization, adjustment to valve stroke 

 

 

The initialization run is switched on by pressing the INIT key (3). 
The valve is completely opened and closed once during 
initialization. LED (2) flashes during initialization. The 
emergency actuator always moves first to the upper end 
position and then to the lower end position. 
The LED remains constantly lit to signal that initialization is 
completed. The INIT key and the LED are located beneath the 
drive hood (see illustration). 
 
 

5. Valve block protection 

Block protection prevents the ball from jamming when the valve is not moved for a longer period of inactivity, 
e.g. for heating systems, during the summer. When block protection is activated, the valve ball is lifted fo several 
seconds if there is no stroke movement for 24 hours. Block protection is not activated when the unit is delivered. 
If plant specifications permit, the valve block protection feature may be activated. Valve block protection can be 
switched on during the initialization phase. 

 
Switch on: 

Valve block protection is switched on and off using switch (1), which is located beneath the drive 

hood. 
 
 

 

 

6. Manual adjustment 

Remove the emergency actuator cover for manual operation. Using the hexagon socket key (key 
socket 4 mm), the valve can be moved into any position. The knob is then used to lock the 
emergency actuator.                                                                                                                                                                                                                                                          

 

 
 
 
 
 
 
 
 
 
 
 
 
 

  

    