7. CALCULATION FORMULAS

7.1 Implementation of Meter Error Correction (Total flow before correction)

Q1 = a

×

Ip

×

(1 + E/100) 

×ε

t

    

where Q

1

: Total flow corrected for meter error

l

a: Meter factor

l/P

Ip: Number of input pulses

E: Meter error correction value

%

The line graph in Fig. 7.1 below shows how meter error curve linearization is achieved. E is approximate-

ly determined by the relationships between input pulse frequency and instrumental error correction value 

set at multipoint error points which are programmable along the flowmeter,s instrumental error curve with 

front-panel keys, and the frequency pulse information (flowrate) currently arriving from the flowmeter.

7.2 Implementation of Temperature/Pressure Correction (Corrected total flow)

Q

2

 = Q

1

×

(P/P

0

)

×

(T

0

/T)

×Χ

 where Q

2

:  Total flow corrected for temperature and pressure

l (normal)

 

Χ

:  (P

a

 

 P

b

 P

c

p

2

) (T

a

 

 T

b

 T

c

t

2

)

 

P:  p 

 0.101325

MPa

abs

 

P

0

:  p

0

 

 0.101325

MPa

abs

 

T:  t 

 273.15

K

 

T

0

:  t

0

 

 273.15

K

 

p:  Line pressure

MPa

 

p

0

:  Correction reference pressure

MPa

 

t:  Line temperature

[℃]

 

t

0

:  Correction reference temperature

[℃

 

 

 

Χ

 is a correction factor as a quadratic factor of temperature and pressure. Constants Pa thru P

c

 and T

a

 

thru T

c

 can be set to any values with keys. Setting P

a

 and T

c

 to 1 while P

b

, P

c

, T

b

, T

c

 to 0 results in 1 at 

all times, permitting calculations according to the Boyle-Charles law. By selecting appropriate values for 

these constants, you can achieve approximate error correction regarding the deviation of gas compress-

ibility factor, etc.

7.3 Instant Flowrate (Uncorrected)
       

Q

m

 = a

×

f

×

(1 + E/100)

×ε

t

×

3600

where Q

m

: Instant flowrate corrected for meter error

l/h

f: Input pulse frequency

Hz

7.4 Instant Flowrate (Corrected)

  

Qmc = Qm

×

(P/P

0

)

×

(T

0

/T)

×Χ

where Q

mc

: Instant flowrate corrected for temperature and pressure

l/h (normal)

0

F

1

F

2

F

3

E

1

E

2

E

3

E

4

F

4

F

8

E

8

E

F

9

9

Fig. 7.1

M

et

er

 e

rro

r

Flowrate

(frequency)

F

1

 thru F

9

 Frequency (Hz)

E

1

 thru E

9

 Meter error correction value (%) Programmable with keys

 

ε

t

 :  Meter,s correction factor relative to temperature

     

 variation

 

 

ε

t

 = 1 + 3

α

(t 

 20)

 

  t = Operating temperature

[℃

 

 

 

 

  3

α

= 4.8

×

10

5

 (stainless steel)

Summary of Contents for EL4121

Page 1: ...knowledge contained in this manual you can expect the best possible results over a long service life of this instrument Keep this manual for ready reference It is suggested that the instruction manual...

Page 2: ...6 INTERNAL COMPONENTS AND FUNCTIONS 9 6 1 Front Panel 9 6 1 1 Display 9 6 1 2 On Screen Menu Items 9 6 1 3 Error Messages 10 6 1 4 Front Panel Keypad 10 7 CALCULATION FORMULAS 11 7 1 Implementation o...

Page 3: ...170 9 EL4501 175 10 DIP SWITCH CONFIGURATION 182 Model with communication capabilities COMMUNICATION MANUAL Ins No E 880CM E CONTENTS 1 COMMUNICATION CAPABILITY OVERVIEW 5 2 NETWORK CONFIGURATION 5 3...

Page 4: ...ou inquire supply complete informa tion as to the product name model number product number ratings and other pertinent information 1 2 Transportation Precautions 1 In order to safeguard against damage...

Page 5: ...n also carry out calculations as a pressure compensator with temperature value fixed 2 1 Features 1 Changing the meter factor ranges of temperature pressure or other parameters of the companion flowme...

Page 6: ...at ambient temperatures up to 50 C it is recommended that the instrument be placed in service at room temperature 3 Provide a sufficient working space behind the instru ment at least 50 centimeters f...

Page 7: ...instrument Fig 4 1 4 3 Description of Terminal Blocks for External Connections Terminal blocks for external connections TB1 TB2 and TB3 are found on the back of the instrument as shown in Fig 4 1 Ter...

Page 8: ...4VAC or 20 to 30VDC 2 N 3 Ground Screws on the terminal block M3 5 Pt100 3 wire 5 PRODUCT CODE EXPLANATION Table 5 1 Item Product Code Description Model E L 4 1 2 1 Temperature pressure compensated fl...

Page 9: ...alibrated for meter error and corrected for temperature and pressure is indi cated 5 Temperature TEMPERATURE The temperature value currently fed to the instrument is indicated If a problem arises in t...

Page 10: ...tion can store a maximum of 20 events each of which consists of year month day hour and minutes of error occurrence and recovery Complete details are covered in the Key Operation Manual 6 1 4 Front Pa...

Page 11: ...273 15 K p Line pressure MPa p0 Correction reference pressure MPa t Line temperature t0 Correction reference temperature is a correction factor as a quadratic factor of temperature and pressure Consta...

Page 12: ...yed NOTE See the KEY OPERATION MANUAL 3 Inject a simulated input pulse train or density signal representing the type of the companion pulse generator 4 Select display menu items of the total mass flow...

Page 13: ...messages PRESS 1 OVER or PRESS 1 UNDER Same also with PRESS 2 1 Input signal line correctly wired 2 Input signal specifications matched 3 System configured correctly 4 Pressure range set correctly 1...

Page 14: ...ty converter circuit error 14 TEMP 1 PT OVER Temperature Pt input 1 overflow 15 TENP 1 PT UNDER Temperature Pt input 1 underflow 16 TEMP 2 PT OVER Temperature Pt input 2 overflow 17 TEMP 2 PT UNDER Te...

Page 15: ...Ckt analog Temp Input Ckt analog Temp Input Ckt Pt Analog Output Circuit Pulse Output Circuit 1 Pulse Output Circuit 2 Pulse Output Circuit 3 Multi plexer Isolation Test Pins Test Pins Internal Volt B...

Page 16: ...rature To the 2nd decimal place when C is selected Pressure To the 4th decimal place when MPa is selected Correction factor To the 4th decimal place Meter error corr factor To the 5th decimal place 3...

Page 17: ...E 882 4 E All specifications are subject to change without notice for improvement 2017 01 Revised 2008 08 Released E 882 4 E 1...

Reviews: