background image

 

900-0127-01-00 Rev B 

15

 

Troubleshooting and Maintenance 

Table 1  Troubleshooting

 

 

Category 

Symptom 

Possible Cause 

Remedy 

Performance 

Reduced operating time 

Normal life cycle 

Replace battery bank when (or before) capacity 

drops to unacceptable levels.  

Defective cells 

Test and replace battery as necessary. 

Excessive voltage drop upon 

applying load 

Excessively cold battery 

Carefully warm up the battery. 

Undersized cabling 

Increase cable ampacity to match loads. 

Loose or dirty cable 

connections 

Check and clean all connections.  Physical 

damage on terminals may require the battery 

to be replaced.  Replace hardware as necessary. 

Undersized battery bank 

Add additional batteries to match loads. 

Defective cells 

Test and replace battery as necessary. 

External 

Inspection 

Swollen or deformed battery 

casing; “rotten-egg” or 

sulfurous odor; battery is hot 

Thermal runaway  

 

NOTE

:  A modest amount of 

swelling (or concavity) on 

the battery case is normal. 

NOTE:

  Thermal runaway is a hazardous 

condition.  Treat the battery with caution.  

Allow the battery to cool before approaching. 

Disconnect and replace battery as necessary.  

Address the conditions that may have led to 

thermal runaway (see page 14).   

Damaged battery casing 

Physical abuse 

Replace battery as necessary. 

Heat damage or melted 

grease at terminals 

Loose or dirty cable 

connections 

Check and clean all connections.  Physical 

damage on terminals may require the battery 

to be replaced.  Replace hardware as necessary. 

Voltage 

testing 

Fully-charged battery 

displays low voltage 

High temperature 

Carefully cool the battery.  An overheated 

battery may contribute to thermal runaway. 

Fully-charged battery 
displays high voltage 

Low temperature 

Carefully warm up the battery. 

Individual battery charging 

voltage will not exceed 

13.3 Vdc; high float current; 

failure to support load 

Shorted cell 

Test and replace battery as necessary.   

A shorted cell may contribute to thermal 

runaway. 

Individual battery float 

voltage exceeds 14.5 Vdc; 
failure to support load 

Open cell 

Test and replace battery as necessary. 

 

 

 

 

Summary of Contents for EnergyCell 170RE

Page 1: ...EnergyCell Front Terminal Battery Owner s Manual ...

Page 2: ...ach Germany Telephone 1 360 435 6030 1 360 618 4363 Technical Support 1 360 435 6019 Fax 49 9122 79889 0 49 9122 79889 21 Fax Email Support outbackpower com Website www outbackpower com Disclaimer UNLESS SPECIFICALLY AGREED TO IN WRITING OUTBACK POWER TECHNOLOGIES a MAKES NO WARRANTY AS TO THE ACCURACY SUFFICIENCY OR SUITABILITY OF ANY TECHNICAL OR OTHER INFORMATION PROVIDED IN ITS MANUALS OR OTHE...

Page 3: ...atures 6 Self Discharge and Freshening 6 Capacity 7 State of Charge 7 System Layout 8 Battery Configurations 8 DC Wiring 10 Charging EnergyCell GH 11 Float Charge 11 Freshening Charge 12 Charging EnergyCell RE 12 Bulk Stage 12 Absorption Stage 12 Float Stage 13 Freshening Charge 13 Notes on EnergyCell RE Charging 13 Temperature Compensation 13 RTS 14 Improper Use 14 Troubleshooting and Maintenance...

Page 4: ... near the batteries Always use insulated tools Avoid dropping tools onto batteries or other electrical parts Keep plenty of fresh water and soap nearby in case battery acid contacts skin clothing or eyes Wear complete eye and clothing protection when working with batteries Avoid touching bare skin or eyes while working near batteries If battery acid contacts skin or clothing wash immediately with ...

Page 5: ...H uses pure lead plates It is intended to receive continuous float charging under normal conditions when utility power is present Intended for use with grid backup float service applications with occasional interruptions but minimal cycling Pure lead plates for long float service life in battery backup applications Extended shelf life 11 1 28 3 cm 4 9 12 6 cm 22 1 56 1 cm The EnergyCell RE uses pa...

Page 6: ...harge and Freshening The EnergyCell battery comes fully charged but will discharge itself over time even in storage Higher storage temperatures increase the rate of self discharge The EnergyCell GH has a longer shelf life than other VRLA batteries including the EnergyCell RE At room temperature 77 F or 25 C the EnergyCell GH has a shelf life of 18 months before self discharging to unacceptable lev...

Page 7: ... a minor degree Smaller loads will deplete the batteries less than larger loads because of this constant replenishment This means that effectively the battery has more capacity under lighter loads For example if the EnergyCell 170RE is discharged at the 48 hour rate a load expected to drain 100 of its capacity in 48 hours it will be measured to have 163 9 amp hours However at the 4 hour rate a hea...

Page 8: ...dc Load Load Load Load Batteries are placed in series negative to positive for additive voltages Batteries in series are known as a string A string of two EnergyCell batteries has a nominal voltage of 24 Vdc and can be used for 24 volt loads A string of four has a nominal voltage of 48 Vdc Other voltages are possible However batteries in series do not have additive amp hours A single string of any...

Page 9: ... 24 Vdc twice the nominal voltage They also have double the amp hour capacity of a single battery Two parallel strings of four batteries in series have a nominal voltage of 48 Vdc at double the amp hour capacity of a single battery In a series parallel bank it is not recommended to connect the load to the positive and negative terminals of a single string Due to cable resistance this will tend to ...

Page 10: ...cable terminations When multiple cables are terminated use plated terminal bus bars Install cable lug or interconnect and all other hardware in the order illustrated The lug or interconnect should be the first item installed It should make solid contact with the mounting surface Do not install hardware in a different order than shown EnergyCell GH Terminals Figure 8 EnergyCell GH Terminals EnergyC...

Page 11: ...nt strings just as was done in step 3 5 Install series connections using the interconnect and hardware that was supplied with each battery The interconnect should connect from the negative left side of battery 1 to the positive right side of battery 2 as shown above Tighten interconnect hardware hand tight only 6 Repeat the process as appropriate for batteries 2 3 and any others in the string Conn...

Page 12: ...ed at a constant high level The battery voltage will rise as long as the current continues to flow Each battery model has a recommended maximum current limit see Table 2 on page 16 which should not be exceeded At excessive current rates the battery s efficiency of conversion becomes less and it may not become completely charged The battery may permanently lose capacity over the long term The purpo...

Page 13: ... absorption voltage should be 14 4 to 14 8 Vdc per battery in a string 2 40 to 2 47 volts per cell If a specialized VRLA charger is available it should charge EnergyCell RE batteries at 14 4 to 14 8 Vdc continuously for 16 hours Notes on EnergyCell RE Charging The current requirements for the absorption and float stages are usually minimal however this will vary with conditions with battery age an...

Page 14: ... the charger settings manually The RTS should be checked periodically Failure to compensate correctly may result in wrong voltages See Improper Use Improper Use CAUTION Equipment Damage Read all items below Maintenance should be performed as noted on page16 Failure to follow these instructions can result in battery damage which is not covered under the EnergyCell warranty CAUTION Equipment Damage ...

Page 15: ...attery case is normal NOTE Thermal runaway is a hazardous condition Treat the battery with caution Allow the battery to cool before approaching Disconnect and replace battery as necessary Address the conditions that may have led to thermal runaway see page 14 Damaged battery casing Physical abuse Replace battery as necessary Heat damage or melted grease at terminals Loose or dirty cable connection...

Page 16: ...orqued before testing If a battery fails any test it may be defective If this occurs under the conditions of the warranty the battery will be replaced according to the terms of the warranty 24 Hour Open Circuit Test Ensure that the battery is brought to a full state of charge Remove all connections from the battery Allow the battery to rest in this state for 24 hours and test its voltage A fully c...

Page 17: ...per battery in series 5 mV per cell per degree C 0 024 Vdc per battery in series 4 mV per cell per degree C Terminal Threaded insert terminal to accept 20 UNC bolt Threaded stud to accept M6 nut Terminal Hardware Initial Torque 110 in lb 12 4 Nm 80 in lb 9 0 Nm Weight 115 0 lb 52 2 kg 131 0 lb 59 4 kg 115 7 lb 52 5 kg Dimensions H x D x W 11 1 x 22 1 x 4 9 28 3 x 56 1 x 12 5 cm 12 6 x 22 0 x 4 9 3...

Page 18: ...tage also depend on the size of the load A load capable of discharging the battery in one hour is far larger than a load which takes 3 4 or 5 hours 8 hour loads 12 hour loads etc are progressively smaller in size As described on page 7 the battery has less capacity under larger loads and more capacity under smaller loads Under a 1 hour load the EnergyCell 170RE has only 89 1 amp hours Under a much...

Page 19: ...Specifications 900 0127 01 00 Rev B 19 This page intentionally left blank ...

Page 20: ...900 0127 01 00 Rev B Corporate Headquarters 17825 59th Avenue N E Suite B Arlington WA 98223 USA 1 360 435 6030 European Office Hansastrasse 8 D 91126 Schwabach Germany 49 9122 79889 0 ...

Reviews: