background image

031-331-B1-001, Rev. A (11/2015)

031-331-B1-001, Rev. A (11/2015)

12

13

Wiring the System, Morningstar TriStar MPPT-30 Charge Controller

3

4

5

Connection detail, charge controller termination board

PV module positive (+) to the charge controller PV positive (+) 

Battery positive (+) from the charge controller to the master DC circuit breaker

Battery negative (–) from the charge controller to the negative bus bar

Charge Controller connections, LEDs, battery sense wiring and remote 

temperature sensor wiring

Battery temperature sensor

 Battery sense positive (+)

 Battery sense negative (–)

3

4

5

To enclosure ground

Illustrations courtesy of Morningstar Corp.

LED indicators

Three LED indicators provide information 

regarding general controller transitions, battery 

status, controller faults and alarms. 

Green

Yellow

Red

A

B

C

D

6

Wiring the System, Morningstar TriStar MPPT-30 Charge Controller

Circuit Breaker Specifications

Wire Size mm

(IEC)

0.75 to 35 mm

2

Wire Gauge (UL)

18 to 2 AWG

Torque (IEC)

2.5 Nm

Torque (UL)

20 in-lb

Comments

Pozidriv #2 Combi head

7

8

9

10

11

12

13

14

15

Battery string connections

String #1 positive (+)

String #2 positive (+)

String #3 positive (+)

String #1 negative (–)

String #2 negative (–)

String #3 negative (–)

Load connections

Battery bus to LVD positive (+)

LVD negative (–) to negative bus bar

LVD (Load) to Load output circuit breaker

DC output voltage positive (+)

DC output voltage negative (–)

Ground connection (–)

Teminal block wiring torque value = 0.9 Nm / 8 in-lb

PV module connections

PV module positive (+)

PV module negative (–) 

Charge Controller connections

PV module positive (+) to charge controller PV positive (+) 

Battery positive (+) from charge controller to DC bus master 
circuit breaker

Battery negative (–) from charge controller to negative bus bar

1

2

3

4

5

A

PV module breaker 

B

DC bus breaker

C

Low voltage disconnect (LVD)

D

Load output breaker

WARNING: Electrical hazard

Only qualified personnel should install and wire the system or have access to the inside of the enclosure.

The system is shipped with the bulk of the wiring connections already in place. Use a #2 Phillips screwdriver to remove the four 
(4) screws that secure the wiring box cover. Verify the pre-existing wiring is still in place and tightened to proper torque settings. 
Replace the cover after inspecting the connections.

6

7

4

3

1

2

12

5

9

11

10

8

13

14

16

Illustration of Morningstar TriStar MPPT-30 Charge Controller courtesy of Morningstar Corp.

17

15

Terminal block torque

 

0.9 Nm / 8 in-lb

16

17

Summary of Contents for smartharvest

Page 1: ...ll Battery Owner s Manual OutBack Power Technologies p n 900 0127 01 00 Audience This guide is intended for experienced installers familiar with the mechanical and electrical requirements of photovolt...

Page 2: ...procedure components could create hazards obstructing free movement and leading to serious bodily injury These hazards are at head eye level The use of head and eye protection is required IMPORTANT T...

Page 3: ...attach the PV module to the rails 1 2 1 2 PV module SmartHarvest Charge Controller connections PV module positive Connect to the lower position of PV input circuit breaker PV module negative Connect...

Page 4: ...acid contacts skin or clothing wash immediately with soap and water If acid enters the eye immediately flood it with running cold water for at least 20 minutes and get medical attention as soon as po...

Page 5: ...Charge Controller connection detail including optional battery sense wiring and remote temperature sensor wiring Battery temperature sensor optional connect to battery terminal Battery sense wire conn...

Page 6: ...ads 2 Recharge battery Yellow LED not on Charge battery Charging to wrong voltage 1 Check position of battery selection jumper 2 Check installation of thermistor Load not powered Check minimum load fo...

Page 7: ...tive String 3 positive String 1 negative String 2 negative String 3 negative Load connections Battery bus to LVD positive LVD negative to negative bus bar LVD Load to Load output circuit breaker DC ou...

Page 8: ...Confirm the polarities of the PV module wiring and Battery string wiring are correct 2 Close the connected battery string breakers 1 through 3 3 Close the master battery disconnect The LEDs on the cha...

Page 9: ...0 Vdc indicating the system is offline A B C D IllustrationofMorningstarTriStarMPPT 30ChargeControllercourtesyofMorningstarCorp A PV module breaker B DC bus breaker C Low voltage disconnect LVD D Load...

Reviews: