PRO208V-5k75 Installation and Safety Manual
900-0203-01-00 Rev B
42
8.
Specifications
8.1.
Power System Specifications
Inverter Specifications
DC Input (2 identical inputs)
Maximum open circuit voltage per String, V
OC
1,000
Vdc
Full power MPPT range, per string
325 to 525 Vdc
PV start voltage
200 Vdc
DC allowable stacking ratio (total, 2 inputs combined)
Must not exceed 8.9 under any circumstances
4
DC maximum input current, per DC input
10 A
DC maximum source short circuit current
30 A
DC maximum input source back feed current to input source
0 A
DC disconnect means
The DC connector has been evaluated and
approved for use as the load-break disconnect
required by the NEC
5
AC Output
AC maximum continuous output power to 45°C
5.75 kW
ac
max
AC de-rate with temperature, 45 to +65°C
–102 W/°C
AC nominal output current, per phase
16.0 A
AC maximum continuous output current, per phase
16.0 A
AC maximum output overcurrent protection
60 A
AC 3-phase system compatibility
208 Vac Wye, 3 phases, neutral and ground
AC voltage range, phase to phase (min / nominal / max)
183 / 208 / 229 V (Limits adjustable, see below)
AC voltage range, phase to neutral (min / nominal / max)
106 / 120 / 132 V (Limits adjustable, see below)
AC operating frequency range (min / nominal / max)
59.3 / 60 / 60.5 Hz (Limits adjustable, see below)
Power Factor
>0.98
AC output waveform
True sine wave
AC lower frequency trip limit
Default
59.3 Hz
+/- 0.1 Hz
Adjustment
57 to 59.8 Hz in 0.1 Hz increments
Clearing time default
0.16 s
+/- 2 cycles
Clearing time adjustment
0.16 to 300 s
AC upper frequency trip limit
Default
60.5 Hz
+/- 0.1 Hz
Adjustment
60.5 to 62.0 Hz in 0.1 Hz
increments
Clearing time default
0.16 s
+/- 2 cycles
Clearing time adjustment
0.16 to 300 s
AC lower voltage trip limit
Default
106 V
+/- 2 %
Adjustment
85 to 106 Vac
Clearing time default
2 s
+/- 2 cycles
Clearing time adjustment
1 to 20 s
AC upper voltage trip limit
Default
132 Vac
+/- 2 %
Adjustment
132 to 144 Vac
Clearing time default
1 s
+/- 2 cycles
Clearing time adjustment
1 to 20 s
AC reconnect delay
Default
5 min
+/- 1 s
Adjustment
1 s to 10 min
4
Stacking: On the DC side of the inverter, each input limits at 3 kW and/or 10A. The combined total AC output is limited to 5.75 kW.
Higher DC STC string powers may be applied. The inverter will limit as described above. Total stacking for inverter must not exceed
8.9 under any circumstances.
5
NEC section 690.17, allowed by the exception of meeting requirements specified in 690.33.