![OutBack Power Alino TL Series Owner'S Manual Download Page 40](http://html1.mh-extra.com/html/outback-power/alino-tl-series/alino-tl-series_owners-manual_1660805040.webp)
Troubleshooting
40
900-0248-01-00 Rev A
Table 8
Error Codes (with unit failure and alarm)
Code
Reason for Failure
Notes
F01
Both of the unit’s fans have failed.
This may require service.
F02
Temperature is too high.
The unit will recover after reaching the set
point in item
07
. (See page 32.)
F03
Battery voltage is too high.
This can be corrected externally.
F04
Battery voltage is too low.
This can be corrected externally.
F05
Output is short-circuited, or internal over-temperature
is detected.
This may be able to be corrected externally.
F06
Output AC voltage is too high.
This may require service.
F07
Overloaded output (timeout has expired) or
overloaded PV input.
The unit will recover after reaching the set
point in item
06
. (See page 32.)
F08
Internal bus voltage is too high.
This may require service.
F09
Internal bus soft start failed.
This may require service.
F51
Overloaded output.
This can be corrected externally.
F52
Internal bus voltage is too low.
This may require service.
F53
Incorrect voltage is present at AC output.
This may require service.
F55
Unbalanced AC output.
This may require service.
F57
Current sensor failed.
This may require service.
F58
Output AC voltage is too low.
This may require service.
F59
PV input voltage is too high.
This can be corrected externally.
Table 9
USB Fault Codes
Code
Reason for Failure
U0
1
No USB device detected.
U02
Device is copy-protected.
U03
Device contains a document with the wrong format.
NOTE:
These codes may appear when a USB device is inserted and a problem is detected.
They appear for 3 seconds before the display returns to the main screen.
Figure
31
Troubleshooting Features
Circuit
Breaker
AC LED Indicator
Fault LED Indicator
Fault codes
(error or
warning)
displayed here
Summary of Contents for Alino TL Series
Page 1: ...Alino TL Power Conditioning Unit Owner s Manual...
Page 45: ...Specifications 900 0248 01 00 Rev A 45 This page intentionally left blank...
Page 46: ...Specifications 46 900 0248 01 00 Rev A This page intentionally left blank...
Page 47: ...Specifications 900 0248 01 00 Rev A 47 This page intentionally left blank...