Specifications
76
900-0169-01-00 Rev A
Default Settings and Ranges
NOTES:
Certain items are retained at the present setting even when the inverter is reset to factory
defaults. These items are noted with the letter “X” in the Item column.
Certain items, particularly those in the Auxiliary menus, share common set points. If one of these
items is changed in a mode menu, all menus with this set point will show the same change.
Certain menus are only visible when the installer password is used, particularly the Grid Interface
Protection menu. These menus are bordered in the table with a double line of this style:
Table 22
FXR Settings for 12-Volt Models
Field
Item Default
Minimum
Maximum
INVERTER
Hot Key
Inverter Mode
Off
On
,
Off
, or
Search
CHARGER
Hot Key
Charger Control
On
On
or
Off
AC Input
Hot Key
AC Input Mode
Use
Drop
or
Use
Search
Sensitivity
(see page 28 for increments)
30 0
200
Pulse Length
8 AC Cycles
4 AC Cycles
20 AC Cycles
Pulse Spacing
60 AC Cycles
4 AC Cycles
120 AC Cycles
AC Input and
Current Limit
Input Type
Grid
Grid
or
Gen
Grid Input AC Limit
30 Aac
2.5 Aac
30 Aac
Gen Input AC Limit
30 Aac
2.5 Aac
30 Aac
Charger AC Limit
FXR2012E
6 Aac
0 Aac
7 Aac
VFXR2612E
8 Aac
0 Aac
9 Aac
Grid AC Input
Mode and Limits
Input Mode
Support
Generator, Support, UPS, Backup, Mini Grid, Grid Zero
Voltage Limit Lower
208 Vac
170 Vac
230 Vac
(Voltage Limit)
Upper
252 Vac
232 Vac
290 Vac
Transfer Delay
1.0 second
0.12 seconds
4.0 seconds
Connect Delay
0.2 minutes
0.2 minutes
25.0 minutes
If
Mini Grid
mode
is selected:
Connect to Grid
12.0 Vdc
11.0 Vdc
16.0 Vdc
(Connect)
Delay
10 minutes
2 minutes
200 minutes
If
Grid Zero
mode
is selected:
DoD Volts
12.5 Vdc
11.0 Vdc
16.0 Vdc
DoD
Amps
FXR2012E
6 Aac
0.5 Aac
8 Aac
VFXR2612E
6 Aac
0.5 Aac
11 Aac
Gen AC Input
Mode and Limits
Input Mode
Generator
Generator, Support, UPS, Backup, Mini Grid, Grid Zero
Voltage Limit Lower
208 Vac
170 Vac
230 Vac
(Voltage Limit)
Upper
252 Vac
232 Vac
290 Vac
Transfer Delay
1.0 second
0.12 seconds
4.0 seconds
Connect Delay
0.5 minutes
0.2 minutes
25.0 minutes
If
Mini Grid
mode
is selected:
Connect to Grid
12.0 Vdc
11.0 Vdc
16.0 Vdc
(Connect)
Delay
10 minutes
2 minutes
200 minutes
If
Grid Zero
mode
is selected:
DoD Volts
12.5 Vdc
11.0 Vdc
16.0 Vdc
DoD
Amps
FXR2012E
6 Aac
0.5 Aac
8 Aac
VFXR2612E
6 Aac
0.5 Aac
11 Aac
AC Output
Output Voltage
X
120 Vac
100 Vac
130 Vac
Low Battery
Cut-Out Voltage
10.5 Vdc
9.0 Vdc
12.0 Vdc
Cut-In Voltage
12.5 Vdc
10.0 Vdc
14.0 Vdc
Battery Charger
Absorb Voltage
14.4 Vdc
11.0 Vdc
16.0 Vdc
(Absorb)
Time
1.0 hours
0.0 hours
24.0 hours
Float Voltage
13.6 Vdc
11.0 Vdc
16.0 Vdc
(Float)
Time
1.0 hours
0.0 hours
24/7
Re-Float Voltage
12.5 Vdc
11.0 Vdc
16.0 Vdc
Re-Bulk Voltage
12.0 Vdc
11.0 Vdc
16.0 Vdc