background image

Connections

900-00270-01-001 REV A  

©2020 OutBack Power.  All Rights Reserved.

Three-Stage Charging

EnergyCell TT batteries are usually charged using a “three-stage” charging cycle: bulk stage, absorption stage, and float 
stage. However, not all chargers are designed or programmed the same way.  The settings should be checked and changed 
to match the recommendations below if necessary.

Bulk Stage

The bulk stage is a constant-current stage.  The charge current is 
maintained at a constant high level.  The battery voltage will rise 
as long as the current flows, raising the battery to a high voltage 
(usually called bulk or absorption voltage).  This typically restores 
the battery to 85 to 90% state of charge (SoC).   This battery has a 
recommended maximum current limit which should not be exceeded.  
See the 

Specifications 

table.

Absorption Stage

The absorption stage is a constant-voltage stage, established upon reaching the bulk target voltage.  The charger maintains 
this voltage as the current decreases until the batteries are full.  A large current is required to reach absorption level.  Less is 
required to maintain it there.  This requirement tends to decrease as long as absorption is maintained.  This decreasing 
current flow typically goes to a very low number (though not zero), known as “return amps”.  This “tops off the tank”, leaving 
the battery at 100% SoC.  The battery is considered to be completely full upon the following conditions:  The charge rate 
must decrease to a level of current equal to between 1% and 3% of the total battery amp-hours 

while maintaining the 

absorption voltage

.  At this point the charger is allowed to exit the absorption stage and enter the next stage.

NOTE

: Not all chargers use return amps. Many chargers absorb for a timed period (one or two hours), assuming that the 

current will decrease to that level.  However, if it exits absorption and ends the charge before reaching return amps, the 
battery may not reach 100% SoC.  Repeated failure to complete the charge will cause decreased battery life.

Float Stage

The float stage is a maintenance stage which provides current to counter the battery’s natural self-discharge.  As with 
absorption, float is a constant-voltage stage which supplies only enough current to maintain the designated voltage.  

Constant-Float Charging

“Constant-float” charging may be used in backup power applications 
where the battery is rarely discharged.  When a discharge occurs, it is 
critical to recharge the battery as soon as possible afterward.  The 
voltage range is listed under 

Specifications

.  The batteries are 

considered fully charged when the voltage is maintained at this level 
and the current drops to a low level over a long period of time.  If using 
a battery monitor device such as an OutBack FLEXnet DC, use the 
settings shown to the right.   

In constant-float charging, it is critical to compensate the charger 
settings for temperature.  

Temperature Compensation

Battery performance changes when the temperature varies above or below room temperature (77°F or 25°C).  When a 
battery is cooler than room temperature, its internal resistance goes up and the battery will be undercharged.  When warmer 
than room temperature, its internal resistance goes down and the battery will tend to be overcharged.  

To compensate, a charger must have its voltages raised by a specified amount for every degree below room temperature, 
or lowered for every degree above room temperature.  For the EnergyCell TT, the required compensation coefficient is 
–0.0033 volts per cell per degree C (–0.0018 V/cell/°F).  This is also multiplied by the number of batteries in a string.

Charging

Series Strings

Batteries wired in series (negative to positive) have additive voltages.  
This is known as a “string”.  In the example below, a string of four 
EnergyCell TT batteries would have a nominal voltage of 48 Vdc.  
However, batteries in series do not have additive amp-hours.

Series / Parallel Strings

Batteries wired in parallel (positive to positive, negative to negative) 
have additive amp-hour capacity.  Placing several strings in parallel 
(series / parallel) gives additive voltages 

and 

capacity.  In the 

example below, the system uses four batteries, but not all are in 
series.  This system uses pairs of batteries in series for 24 volts.  
Two pairs are shown in parallel for double the amp-hours.

NOTE: 

 Consult a professional installer before connecting more than 

three strings in parallel.

Hardware

EnergyCell TT terminals consist of a 
threaded hole which receives an 
M6 × 12 mm bolt.  Terminal hardware 
is assembled as shown in this image.

Bulk

Bulk

Absorption

Absorption

Float

Float

DC 

Volts

Amperes 

(typical)

Hours (typical)

Hours (typical)

15

14

13

12

11

10

20

15

10

5

0

–5

1  

    2  

   3

 

1  

    2  

   3

 

Charging Graphs

Charging Voltages 

(multiplied by the 

number of batteries in a series string)

o

Absorb Charging Voltage

:  14.4 to 15.0 Vdc

o

Equalize Charging Voltage

:  15.0 Vdc

(16 hours every 2 months or 25 cycles)

o

Float Voltage

: 13.5 to 13.8 Vdc

Settings

o

Battery Amp-Hours

: Based on the rated

20-hour capacity (see 

Specifications

)

o

Charged Voltage

: 14.0 Vdc

(0.4 volts below absorption setting)

o

Charged Return Amps

: 1 to 3% Adc

o

Time

: 1 minute

o

Charge Factor

: 97%

M6 Bolt

Lock Washer

Flat Washer

Cable Lug or 

Interconnect

Battery Terminal 

Surface

Positive (+)

Negative (–)

Positive (+)

Negative (–)

Summary of Contents for EnergyCell TT Series

Page 1: ... the internal electrochemical reactions and the resistivity of the electrolyte It is depicted in the Capacity vs Temperature graph Note that battery cycle life is also affected by depth of discharge as shown in the Cycle Life graph Operating Conditions EnergyCell TT batteries are valve regulated and sealed They do not give off perceptible amounts of gas under normal operating conditions o Operatin...

Page 2: ...ations The batteries are considered fully charged when the voltage is maintained at this level and the current drops to a low level over a long period of time If using a battery monitor device such as an OutBack FLEXnet DC use the settings shown to the right In constant float charging it is critical to compensate the charger settings for temperature Temperature Compensation Battery performance cha...

Page 3: ...the battery grease and reassemble the connection If there is obvious leakage replace batteries as necessary Symptoms and Remedies Symptom Possible Cause Possible Remedy System float voltage greater than 13 8 volts Charger voltage set too high Reset charger output voltage to recommended values per battery at 77 F 25 C System float voltage Reset charger output voltage to recommended values less than...

Page 4: ...s with low capacity Replace afflicted batteries voltage decline or plateaus AC ripple voltage p p is greater than 4 of the value Poor filtering of charger output Improve charger output filtering of the DC float voltage Individual battery exhibits Proportionately higher impedance AC ripple voltage twice that due to deteriorating material or Replace afflicted batteries Evaluate the entire string of ...

Reviews: