INSTALLATION GUIDE

Product code

I

n Al

I

n Cu

U

n

I

max Al

I

max Cu

U

max

VC03-0003

560 A

560 A

690 V

-

-

-

Type

Screw

Thread

M12

Tightening torque

185-300 mm²

70 Nm

 Stripping length 

L

40±2 mm

 SW

6

-

-

-

-

-

-

Max. Wire cross section

300 mm²

1,5 mm

2

2,5 mm

2

6 mm

2

10 mm

2

16 mm

2

25 mm

2

35 mm

2

50 mm

2

-

-

-

-

-

-

-

-

70 mm

2

95 mm

2

120 mm

2

150 mm

2

185 mm

2

240 mm

2

300 mm

2

400 mm

2

-

-

-

-

1(1)

1(1)

1(1)

-

Ouneva Oy

Teollisuustie 21
FI-82730 Tuupovaara

Tel. +358 400 179 750

www.ounevagroup.fi

Finland

[email protected]

www.ounevaproducts.fi

Product data

Product name

OLE 185-300

Installation

Screw  

Cross-section of conductors and number of conductors / space. (Al-conductors in parenthesis) 

Connection

SW

Note! The specified amount of  
conductors refers only to industrially 

installed terminals.

L

Opening the enclosure

Carefully lift the lid 
from the marked spots

Screw mounting

Max. Screw  Ø 6,2

It is possible to connect several
connectors together with screw
connection. (Screw size Ø 5,4)

Mounting to busbar
-Recommended torque for M10: 30-44Nm

Installation

Can be used for both 

copper- or aluminium 

conductors

. With the Al-conductors, It's 

recommended to use anti-corrosion paste. (e.g. 

Penetrox).

It is allowed to use max. of three adjacent 

cross-sections in one space (Copper 

conductors). The nominal max. cross-section 

value must not be exceeded.

When used Al-conductors, it is allowed to use 

only one conductor / space.

We recommend a ferrule when using a fine-

stranded conductor.

70 Nm

M10/8.0/DIN 934

M10/DIN 6796

M10x25/8.8/DIN 933