F A U L T D E T E C T I O N
1. Make sure that there is tension to the fan.
2. Cut the tension and verify that the impeller is not
blocked.
3. Check the thermo-contact/motor protector. If it is
disconnected the cause of overheating must be
taken care of, not to be repeated.
At automatic thermo-contact the resetting will be
done automatically when the motor is cold.
4. Make sure that the capacitor is connected, (single
phase only) according to the wiring diagram.
5. If the fan still does not work, the first thing to do is
to renew the capacitor.
6. If nothing of this works, contact your fan supplier.
7. If the fan is returned to the supplier, it must be
cleaned, the motor cable undamaged and a detailed
nonconformity report enclosed.
W A R R A N T Y
36