LED  Relays K1

Cause

Reaction of Controller

Adjustment

Code

(for function

Explanation

factory setting)

3 x

De-energized,

HALL-IC

Controller turns the motor off.

terminals

Incorrect signal from the Hall-ICs,

Automatic restart if no more

11-14

error in the commutation.

fault is recongized.

interrupted.

4 x

De-energized,

Line failure 

(only for 3 ~ types)

terminals

The device is provided with a built-in Following a shut off, a start up Checking power 

11-14

phase-monitoring function for the

attempt is made after approxi- supply.

interrupted.

mains supply. In the event of a mains

mately 15 seconds, if the

interruption (failure of a fuse or

voltage supply is high enough.

mains phase) the unit switches off

This keeps occurring until all

after a delay (approx. 200 ms).

3 supply phases are available

Function only when load for the con- again.
troller is high enough.

5 x

De-energized,

Motor blocked

EC-Controller switches off,

Check if motor 

terminals

If after 8 seconds cummutation no

renewed attempt to start after

is freely rotatable.

11-14

speed is measured > 0, the fault

about 2,5 sec. Final shut off,

interrupted.

”Motor blocked” is released.

when fourth starting test fails.
It is then necessary to have an
enabling reset or to disconnect
the power supply.

6 x

De-energized,

IGBT Fault

EC-Controller switches off,

terminals

Shortcut earth or shortcut of motor

renewed attempt to start after

11-14

winding.

about 60 sec.

Code 9.

interrupted.

Final shutoff, if - following a 
second starting test – a second 
fault detection is detected 
within a period of 60 seconds.

7 x

De-energized,

DC undervoltage

If the intermediate circuit

terminals

If the voltage drops below a specified voltage rises again within

11-14

limit, the device is shut off.

75 seconds above the limit, an

interrupted.

automatic starting test is run.
If the intermediate circuit vol-
tage remains below the limit 
for more than 75 seconds, the 
device is shut off with a fault 
message.

8 x

De-energized,

DC overvoltage

If the intermediate circuit

terminals

If the voltage increases below a

voltage drops again within

11-14

specified limit, the motor is switched

75 seconds below the limit, an

interrupted.

off. Reason for excessively high input

automatic starting test is run.

voltage or alternator motor operation. If the intermediate circuit vol-

tage remains above the limit 
for more than 75 seconds, the 
device is shut off with a fault 
message.

9 x

Energized,

IGBT cooling down period

terminals

IGBT cooling down period for  

11-14

approx. 60 sec.

bridged.

Final shut off after 2 cooling-off 
intervals 

Code 6.

30

Summary of Contents for RKB 1000x500 C3 EC

Page 1: ...VENSK ENGLISH VERSION Bruksanvisning Directions for use RKB 300x150 B1 EC RKB 400x200 C1 EC RKB 500x250 D1 EC RKB 600x300 A1 EC RKB 600x350 A1 EC RKB 700x400 B3 EC RKB 800x500 B3 EC RKB 1000x500 C3 EC...

Page 2: ...e produktens anv ndning av en person ansvarig f r deras s kerhet Barn skall h llas under uppsikt f r att f rs kra att de inte leker med produkten Fl kten ska anv ndas f r transport av ren luft m a o d...

Page 3: ...beh rig installat r Elinstallation ska ske via allpolig str mbrytare i n ra anslutning till fl kten eller via l sbar huvudstr m brytare I enfasfl ktar anv nds jordfelsbrytare typ A I 3 fasfl ktar anv...

Page 4: ...4 K O P P L I N G S S C H E M A 4 0 4 0 1 4 4 Enfas 230 V 4 0 4 0 1 4 3 Enfas 230V 4 0 4 0 1 4 5 Enfas 230 V L3 L2 4 0 4 0 1 4 7 3 fas 400 V Larm Larm Larm...

Page 5: ...s 220 Pa Omgivning 54 61 28 41 52 56 56 51 48 44 Inlopp 73 53 62 67 68 64 62 64 56 Utlopp 77 56 64 69 69 71 70 69 62 6 V 80 l s 160 Pa Omgivning 49 56 25 33 45 50 53 47 43 40 Inlopp 69 50 57 64 64 60...

Page 6: ...g 38 45 29 32 43 33 39 30 28 28 Inlopp 56 51 52 50 43 42 36 35 18 Utlopp 61 50 58 54 47 47 44 43 22 RKB 600x300 A1 EC 10 V 630 l s 250 Pa LpA LwA tot dB A 63 125 250 500 1K 2K 4K 8K Omgivning 60 67 40...

Page 7: ...9 56 37 53 52 44 44 38 34 32 Inlopp 69 59 67 63 54 51 54 53 48 Utlopp 72 60 67 68 61 59 59 56 54 RKB 700x400 B3 EC 10 V 1800 l s 250 Pa LpA LwA tot dB A 63 125 250 500 1K 2K 4K 8K Omgivning 68 75 56 6...

Page 8: ...47 54 49 49 49 46 42 36 34 31 Inlopp 67 58 63 57 52 56 56 58 44 Utlopp 71 59 65 64 60 62 61 61 52 8 RKB 1000x500 C3 EC 10 V 3100 l s 500 Pa LpA LwA tot dB A 63 125 250 500 1K 2K 4K 8K Omgivning 71 78...

Page 9: ...G R A M E F F E K T F L D E RKB 300x150 B1 EC RKB 400x200 C1 EC T R Y C K F L D E RKB 300x150 B1 EC RKB 400x200 C1 EC T R Y C K F L D E RKB 500x250 D1 EC RKB 600x300 A1 EC E F F E K T F L D E RKB 500...

Page 10: ...G R A M E F F E K T F L D E RKB 600x350 A1 EC RKB 700x400 B3 EC T R Y C K F L D E RKB 600x350 A1 EC RKB 700x400 B3 EC T R Y C K F L D E RKB 800x500 B3 EC RKB 1000x500 C3 EC E F F E K T F L D E RKB 800...

Page 11: ...RKB 300x150 B1 EC RKB 400x200 C1 EC RKB 500x250 D1 EC RKB 600x300 A1 EC RKB 600x350 A1 EC RKB 700x400 B3 EC RKB 800x500 B3 EC RKB 1000x500 C3 EC 11 M T T S K I S S E R mm...

Page 12: ...0 C3 EC F r mer information se sidan 13 14 4 Om ingen av dessa tg rder hj lper kontakta din fl ktleverant r 5 Vid ev reklamation skall fl kten vara rengjord motorkabeln vara oskadad och en utf rlig fe...

Page 13: ...ellan D1 och sluten Digital In 1 ej sluten 24 V 10 V 2 x Rel draget Aktiv temperatur vervakning terminals Enheten har en aktiv temperatur ver Vid sjunkande temperatur Kontrollera 11 14 vakning f r att...

Page 14: ...rde f rs ket miss lyckats D r det n dv ndigt att enkelt kunna terst lla eller st nga av str mmen 6 x Rel ej draget IGBT Fel EC enheten st ngs av anslutning Kortslutning mot jord eller kortslut nya f...

Page 15: ...iknande bruksf rem l S kerhet Del 2 8 S rskilda fordringar p fl ktar Direktivet f r elektromagnetisk kompatibilitet EMC 2004 108 EG Harmoniserande standarder SS EN 61000 6 1 2007 Elektromagnetisk komp...

Page 16: ...erous substances explosives grinding dust soot etc To achieve maximum life time for installations in damp or cold environments the fan should be ope rating continuously The fan can be installed outsid...

Page 17: ...made by an authori zed electrician Electrical installations must be connected to a local ly situated tension free switcher or by a lockable head breaker For single phase fans a residual current circu...

Page 18: ...20 W I R I N G D I A G R A M 4 0 4 0 1 4 4 Single phase 230 V 4 0 4 0 1 4 3 Single phase 230V 4 0 4 0 1 4 5 Single phase 230 V L3 L2 4 0 4 0 1 4 7 3 phase 400 V Alarm Alarm Alarm...

Page 19: ...3 69 70 68 63 66 58 Outlet 78 56 65 69 71 72 72 71 64 8 V 95 l s 220 Pa Environment 54 61 28 41 52 56 56 51 48 44 Inlet 73 53 62 67 68 64 62 64 56 Outlet 77 56 64 69 69 71 70 69 62 6 V 80 l s 160 Pa E...

Page 20: ...nt 38 45 29 32 43 33 39 30 28 28 Inlet 56 51 52 50 43 42 36 35 18 Outlet 61 50 58 54 47 47 44 43 22 RKB 600x300 A1 EC 10 V 630 l s 250 Pa LpA LwA tot dB A 63 125 250 500 1K 2K 4K 8K Environment 60 67...

Page 21: ...t 49 56 37 53 52 44 44 38 34 32 Inlet 69 59 67 63 54 51 54 53 48 Outlet 72 60 67 68 61 59 59 56 54 RKB 700x400 B3 EC 10 V 1800 l s 250 Pa LpA LwA tot dB A 63 125 250 500 1K 2K 4K 8K Environment 68 75...

Page 22: ...ent 47 54 49 49 49 46 42 36 34 31 Inlet 67 58 63 57 52 56 56 58 44 Outlet 71 59 65 64 60 62 61 61 52 RKB 1000x500 C3 EC 10 V 3100 l s 500 Pa LpA LwA tot dB A 63 125 250 500 1K 2K 4K 8K Environment 71...

Page 23: ...S 25 P R E S S U R E F L O W RKB 300x150 B1 EC RKB 400x200 C1 EC P R E S S U R E F L O W RKB 300x150 B1 EC RKB 400x200 C1 EC P R E S S U R E F L O W RKB 500x250 D1 EC RKB 600x300 A1 EC P R E S S U R E...

Page 24: ...26 P R E S S U R E F L O W RKB 600x350 A1 EC RKB 700x400 B3 EC P R E S S U R E F L O W RKB 600x350 A1 EC RKB 700x400 B3 EC P R E S S U R E F L O W RKB 800x500 B3 EC RKB 1000x500 C3 EC P R E S S U R E...

Page 25: ...27 D I M E N S I O N S mm RKB 300x150 B1 EC RKB 400x200 C1 EC RKB 500x250 D1 EC RKB 600x300 A1 EC RKB 600x350 A1 EC RKB 700x400 B3 EC RKB 800x500 B3 EC RKB 1000x500 C3 EC...

Page 26: ...e fan high pressure cleaning or strong dissolvent must not be used Cleaning should be done without dislodging or damaging the impeller Make sure that there is no noise from the fan O P E R A T I O N W...

Page 27: ...bridged Digital In 1 not bridged 2 x Energized Active temperature monitoring terminals The device has an active temperature At sinking temperature the Check cooling 11 14 monitoring to protect it fro...

Page 28: ...necessary to have an enabling reset or to disconnect the power supply 6 x De energized IGBT Fault EC Controller switches off terminals Shortcut earth or shortcut of motor renewed attempt to start afte...

Page 29: ...pliances Part 2 80 Particular requirements for fans Directive for Electromagnetic Compatibility EMC 2004 108 EG Harmonised standards SS EN 61000 6 1 2007 Electromagnetic compatibility EMC Generic stan...

Page 30: ...1270279 utg 2 AB C A STBERG Box 54 SE 774 22 Avesta Sweden Industrigatan 2 Avesta Tel 46 226 860 00 Fax 46 226 860 05 Email info ca ostberg se www ostberg com...

Reviews: