OSTBERG LPK Series Installation And Directions For Use Download Page 5

S O U N D   D A T A

LPK 4” A, 64 CFM, 0,5 H

2

O

L

pA

L

wA

tot dB (A)

63

125

250

500

1K

2K

4K

8K

To environment

42

49

20

28

39

37

43

47

33

27

Inlet

58

38

50

46

52

52

48

46

42

Outlet

62

48

54

52

54

58

53

50

45

LPK 4” B, 131 CFM, 0,5 H

2

O

L

pA

L

wA

tot dB (A)

63

125

250

500

1K

2K

4K

8K

To environment

48

55

23

33

46

45

51

50

42

37

Inlet

67

46

59

57

63

59

56

56

55

Outlet

73

56

62

63

66

66

64

62

61

LPK 5” A, 95 CFM, 0,3 H

2

O

L

pA

L

wA

tot dB (A)

63

125

250

500

1K

2K

4K

8K

To environment

40

47

28

34

39

39

43

41

32

25

Inlet

57

41

48

50

53

50

46

47

32

Outlet

62

46

54

54

55

56

50

55

39

LPK 5” B, 144 CFM, 0,7 H

2

O

L

pA

L

wA

tot dB (A)

63

125

250

500

1K

2K

4K

8K

To environment

47

54

23

37

45

45

50

48

40

33

Inlet

66

47

56

59

62

57

54

53

49

Outlet

71

53

64

63

65

65

61

60

56

LPK 6” B, 205 CFM, 0,6 H

2

O

L

pA

L

wA

tot dB (A)

63

125

250

500

1K

2K

4K

8K

To environment

50

57

29

45

47

48

53

52

46

39

Inlet

71

56

64

67

64

58

56

58

56

Outlet

74

58

63

68

67

67

60

63

61

LPK 6” D, 220 CFM, 1,1 H

2

O

L

pA

L

wA

tot dB (A)

63

125

250

500

1K

2K

4K

8K

To environment

50

57

37

47

48

49

50

50

48

46

Inlet

74

52

64

70

69

61

60

61

61

Outlet

78

61

68

73

73

70

67

66

66

The sound data have been compiled by means of sound
measurements methods as follows:
Pressure and drop: SS-ISO 5801.
Determination of acoustic sound level in duct:
SS-EN ISO 5136.
Determination of acoustic sound level in reverberation
room: SS-EN ISO 3741.

D E S I G N A T I O N S

LwATot

: Total A-weighted sound power level dB(A)

(ref 10

-12

W)

=

the sum of the sound power level in the

octave ranges.

LwA

: A-weighted sound power level in octave range

dB(A)(ref 10

-12

W).

LpA

: A-weighted sound pressure level in dB(A) accor-

ding to normed A-weightening correction and relating
to an effective absorption area of 20 m

2

with half sphe-

rical translation at a distance of 3 metres.

5

1270140_LPK_UL_utg1.qxp  2009-09-04  10:23  Sida 5

Summary of Contents for LPK Series

Page 1: ...UL VERSION Installation and directions for use Low profile duct fan LPK 1270140_LPK_UL_utg1 qxp 2009 09 04 10 23 Sida 1...

Page 2: ...the inside of the junction box Use this unit only in the manner intended by the manufacturer If you have any questions contact your manufacturers representative Before servicing and cleaning unit swit...

Page 3: ...ur manufacturers representative Before service and cleaning of the unit switch off the power at the service panel and lock the service disconnecting means to prevent power from being switched on accid...

Page 4: ...60 0 94 107 1500 3 8 4040076 8 F IP 44 LPK 6 B 115 60 1 33 143 1895 4 4 4040076 16 F IP 44 LPK 6 D 115 60 1 63 186 2155 4 6 4040076 16 F IP 44 W I R I N G D I A G R A M S Fanmotor Green White Black R...

Page 5: ...8K To environment 50 57 29 45 47 48 53 52 46 39 Inlet 71 56 64 67 64 58 56 58 56 Outlet 74 58 63 68 67 67 60 63 61 LPK 6 D 220 CFM 1 1 H2O LpA LwA tot dB A 63 125 250 500 1K 2K 4K 8K To environment 5...

Page 6: ...6 P R E S S U R E A N D F L O W D I A G R A M S LPK 4 A B LPK 5 A B LPK 6 B D 1270140_LPK_UL_utg1 qxp 2009 09 04 10 23 Sida 6...

Page 7: ...Exhaust system Exhaust system for ceiling Exhaust system The LPK fan can easily be mounted with the four brackets in any position Installation instructions for exhaust systems for duct fan type LPK 7...

Page 8: ...1270140UL 0906 Utg 1 OSTBERG AMERICAS INC 55 Raglin PL 3 Cambridge N1R 7J2 Canada Phone 519 623 6363 Telefax 519 623 8543 www ostberg com 1270140_LPK_UL_utg1 qxp 2009 09 04 10 23 Sida 8...

Reviews: