53
S E R V I C E M E N U : “ A C F A N S E T U P ” :
(
Not used
)
When adjusting the unit, the speed is set to
standard and functions that may affect the
fan speed, such as “Away” and “Boost”,
is inactivated.
S E R V I C E M E N U : “ F I L T E R M E A S U R E M E N T ”
Filter measurement HERU
®
EC
without
CPC:
Filter measurement becomes active when ”Filter control” is selec-
ted in menu ”Pressure inputs”.
If filter switches are installed and activated, weekday and time is set when the unit
should boost to measure the pressure drop in supply air filter
GP1
and exhaust air filter
GP2
.
HERU
®
EC
with
CPC:
Filter measurement becomes active if the analog pressure sensor is choosed and CPC
(Constant Pressure Control) is activated, and benchmarks are set and saved.
Alarm is displayed when the bench-
marks and increased fan speed exceeded set value. In this case with 15% to keep constant pressure in duct. It is
possible to choose
5-50%
increased speed or ”
Off”
to deactivate.
HERU
®
AC (Not used):
If filter switches are installed and activated, weekday and time is set when the unit
should boost to measure the pressure drop in supply air filter
GP1
and exhaust air filter
GP2
.
If
no
filter switches or pressure sensor are selected this is displayed:
S E R V I C E M E N U : “ E C F A N S E T U P ” :
(
Only
for HERU
®
EC)
Fan speed settings for EC fans. No CPC.
The relation between supply and extract air is also retained at the other speeds.
The ratio between supply and extract air is adjusted only in standard mode.
CPC (Constant Pressure Control) deactivated.
With the CPC activated the set value is displayed (current value).
To change set value choose
”To Constant pressure
”.
See ”Constant pressure” page 52.
Servicemeny
Filtermätning
EC-motor setup
Display kontrast
Är du säker?
Bör endast ändras
av installatör!
Standard (%)
Tilluft: 60%
Frånluft: 70%
Minimum
Min: 20%
EC-motor setup
Standard
Min
Medium
Avbryt Ok
Standard (konst.tr.)
Till: 90Pa (45%)
Från: 110Pa (50%)
Till konst.tr.
EC-motor setup
Standard
Min
Medium
Minimum
Min: 20%
Standard (%)
Tilluft: 60%
Frånluft: 70%
Standard (%)
Tilluft: 60%
Frånluft: 70%
Pressure inputs
Pressure inputs
Filter measurement
Filter measurement
EC fan setup
EC fan setup
Display contrast
Display contrast
Enter
Are you sure?
Are you sure?
Should not be
Should not be
changed by user!
changed by user!
Standard (%)
Standard (%)
Sup: 60%
Sup: 60%
Exh: 70%
Exh: 70%
Enter
Minimum
Min: 20%
EC fan setup
EC fan setup
Standard
Standard
Min
Min
Medium
Medium
Cancel Ok
Cancel Ok
Standard (CPC)
Sup: 90Pa (45%)
Exh: 110Pa (50%)
Go to CPC
A
EC fan setup
Standard
Min
Medium
Minimum
Min: 20%
Standard (%)
Sup: 60%
Exh: 70%
Standard (%)
Sup: 60%
Exh: 70%
Servicemeny
Filtermätning
EC-motor setup
Display kontrast
Är du säker?
Bör endast ändras
av installatör!
Standard (%)
Tilluft: 60%
Frånluft: 70%
Minimum
Min: 20%
EC-motor setup
Standard
Min
Medium
Avbryt Ok
Standard (konst.tr.)
Till: 90Pa (45%)
Från: 110Pa (50%)
Till konst.tr.
EC-motor setup
Standard
Min
Medium
Minimum
Min: 20%
Standard (%)
Tilluft: 60%
Frånluft: 70%
Standard (%)
Tilluft: 60%
Frånluft: 70%
Pressure inputs
Filter measurement
EC fan setup
Display contrast
Are you sure?
Should not be
changed by user!
Standard (%)
Sup: 60%
Exh: 70%
Minimum
Minimum
Min: 20%
Min: 20%
Enter
EC fan setup
Standard
Min
Medium
Cancel Ok
Standard (CPC)
Sup: 90Pa (45%)
Exh: 110Pa (50%)
Go to CPC
EC fan setup
EC fan setup
Standard
Standard
Min
Min
Medium
Medium
Minimum
Minimum
Min: 20%
Min: 20%
Enter
Up
Down
Standard (%)
Sup: 60%
Exh: 70%
Standard (%)
Sup: 60%
Exh: 70%
Servicemeny
Filtermätning
EC-motor setup
Display kontrast
Är du säker?
Bör endast ändras
av installatör!
Standard (%)
Tilluft: 60%
Frånluft: 70%
Minimum
Min: 20%
EC-motor setup
Standard
Min
Medium
Avbryt Ok
Standard (konst.tr.)
Till: 90Pa (45%)
Från: 110Pa (50%)
Till konst.tr.
EC-motor setup
Standard
Min
Medium
Minimum
Min: 20%
Standard (%)
Tilluft: 60%
Frånluft: 70%
Standard (%)
Tilluft: 60%
Frånluft: 70%
Pressure inputs
Filter measurement
EC fan setup
Display contrast
Are you sure?
Should not be
changed by user!
Standard (%)
Sup: 60%
Exh: 70%
Minimum
Min: 20%
EC fan setup
Standard
Min
Medium
Cancel Ok
Standar
Standard (CPC
(CPC)
Sup: 90Pa (45%)
Sup: 90Pa (45%)
Exh: 110Pa (50%)
Exh: 110Pa (50%)
Go to CPC
Go to CPC
EC fan setup
Standard
Min
Medium
Minimum
Min: 20%
Standard (%)
Sup: 60%
Exh: 70%
Standard (%)
Sup: 60%
Exh: 70%
Servicemeny
Filtermätning
EC-motor setup
Display kontrast
Är du säker?
Bör endast ändras
av installatör!
Standard (%)
Tilluft: 60%
Frånluft: 70%
Minimum
Min: 20%
EC-motor setup
Standard
Min
Medium
Avbryt Ok
Standard (konst.tr.)
Till: 90Pa (45%)
Från: 110Pa (50%)
Till konst.tr.
EC-motor setup
Standard
Min
Medium
Minimum
Min: 20%
Standard (%)
Tilluft: 60%
Frånluft: 70%
Standard (%)
Tilluft: 60%
Frånluft: 70%
Pressure inputs
Filter measurement
EC fan setup
Display contrast
Are you sure?
Should not be
changed by user!
Standard (%)
Sup: 60%
Exh: 70%
Minimum
Min: 20%
EC fan setup
Standard
Min
Medium
Cancel Ok
Standard (CPC)
Sup: 90Pa (45%)
Exh: 110Pa (50%)
Go to CPC
EC fan setup
Standard
Min
Medium
Minimum
Min: 20%
Standard (%)
Standard (%)
Sup: 60%
Sup: 60%
Exh: 70%
Exh: 70%
Enter
Up
Down
Standard (%)
Standard (%)
Sup: 60%
Sup: 60%
Exh: 70%
Exh: 70%
Enter
Up
Down
Cont.
Cont. next line.
(Sup: 16%)
Exh: 20%
Servicemeny
Filtermätning
EC-motor setup
Display kontrast
Är du säker?
Bör endast ändras
av installatör!
Standard (%)
Tilluft: 60%
Frånluft: 70%
Minimum
Min: 20%
EC-motor setup
Standard
Min
Medium
Avbryt Ok
Standard (konst.tr.)
Till: 90Pa (45%)
Från: 110Pa (50%)
Till konst.tr.
EC-motor setup
Standard
Min
Medium
Minimum
Min: 20%
Standard (%)
Tilluft: 60%
Frånluft: 70%
Standard (%)
Tilluft: 60%
Tilluft: 60%
Frånluft: 70%
Frånluft: 70%
Pressure inputs
Filter measurement
EC fan setup
Display contrast
Are you sure?
Should not be
changed by user!
Standard (%)
Sup: 60%
Exh: 70%
Minimum
Min: 20%
EC fan setup
Standard
Min
Medium
Cancel Ok
Standard (CPC)
Sup: 90Pa (45%)
Exh: 110Pa (50%)
Go to CPC
EC fan setup
Standard
Min
Medium
Minimum
Min: 20%
Standard (%)
Sup: 60%
Exh: 70%
Standard (%)
Sup: 60%
Exh: 70%
(Sup: 16%)
Exh: 20%
Service menu
Servicemeny
Servicemeny
Filtermätning
Filtermätning
EC-motor setup
EC-motor setup
Display kontrast
Display kontrast
Är du säker?
Bör endast ändras
av installatör!
Standard (%)
Tilluft: 60%
Frånluft: 70%
Minimum
Min: 20%
EC-motor setup
EC-motor setup
Standard
Standard
Min
Medium
Medium
Avbryt Ok
Standard (konst.tr.)
Till: 90Pa (45%)
Från: 110Pa (50%)
Till konst.tr.
EC-motor setup
Standard
Min
Medium
Minimum
Min: 20%
Standard (%)
Tilluft: 60%
Frånluft: 70%
Standard (%)
Tilluft: 60%
Frånluft: 70%
Pressure inputs
Filter measurement
EC fan setup
Display contrast
Are you sure?
Should not be
changed by user!
Standard (%)
Sup: 60%
Exh: 70%
Minimum
Min: 20%
EC fan setup
Standard
Min
Medium
Cancel Ok
Standard (CPC)
Sup: 90Pa (45%)
Exh: 110Pa (50%)
Go to CPC
EC fan setup
Standard
Min
Medium
Minimum
Min: 20%
Standard (%)
Sup: 60%
Exh: 70%
Standard (%)
Sup: 60%
Exh: 70%
--Fan speed--
Standard
Service menu
Service menu
Service menu
Ext:
Ext:
Ext:
Ext:
Filter measurement
AC fan setup
Display contrast
1270411_utg4_HERU_LP_SV_EN.indd 53
2019-03-04 08:15:59
1270411_utg4_HERU_LP_SV_EN.pdf 53
2019-03-04 08:20:48
Summary of Contents for HERU LP
Page 10: ...10 REGLERSCHEMA HERU LP som visar samtliga givare fl desriktning h ger...
Page 32: ...32...
Page 33: ...33...
Page 44: ...44 CONTROL DIAGRAM HERU LP shows all sensors flow direction right...
Page 66: ...66 66...
Page 67: ...67 67...
Page 78: ...78...
Page 79: ...79...