Troubleshooting, alarm:
Observation indication
Cause/action
Check that the DIP switches are
correctly set
DIP switch “ON” to the left.
No LED illuminates
Check that 230 VAC ±10% is on the mains terminal.
If the mains voltage is correct, replace the control unit.
Rotation alarm
• Belt broken
• Belt dislodged
• Rotor stuck
• Magnet sensor or magnet not intact
Overvoltage
The feed voltage is above 265 V. Ensure correct voltage to the unit.
Undervoltage
The feed voltage is below 190 V. Ensure correct voltage to the unit.
Over/under temperature
The temperature in the control unit is above +85°C or below -30°C.
Short circuit
• Short circuit between phases in cable or motor
• Earth fault between phase-earth in cable or motor
• Interrupt in one phase in cable or motor (measure motor resistance,
should be the same on all windings)
Internal fault
Internal control fault has occurred.
The motor is difficult to start-up,
weak
Check that the phase order is correct according to the wiring diagram.
GENERAL
This section describes functions and settings for time switch programs and calendars.
When no object with higher priority (for example Manual mode <> Auto) is enabled,
the unit can be switched off or the stage changed (stage1...3) via the time switch pro-
gram. Up to six switching times can be specified for each day of the week.
Calendar stop overrides calendar exception, which in turn overrides the normal time
switch program (only in operating mode). Up to 10 periods or exception days can be
specified for each calendar.
Time switch program.funct. = Stage+Temp: Setpoints for both fan stage and tempera-
ture (comfort/economy) are controlled by the time switch program.
WEEK SCHEDULE
Main index > Unit > Operating functions > Time switch program > Schedule
Parameter
Value
Function
Current value
–
Switch over according to schedule.
Monday
Shows current command when the current day is Monday.
The latest time that can be entered for a day is 23:59.
Go to the daily switching schedule for Mondays.
Copy
schedule
– Mon. to
– Tue–Fri
Copy times for the time switch program from Monday to Tuesday-Friday.
– Passive (no copying).
– Copying starts. Returning to the display screen.
Tuesday
Same functions as for Monday.
Sunday
Same functions as for Monday.
Exception
Shows current command when the current day is an exception day.
Go to daily switching schedule for exception days.
Period: Start
(Only authority level 2.) Start date for week schedule. *,* *.00 means that the
week schedule is always enabled. --> Activate week schedule.
Period: End
(Only authority level 2.)
Start date and start time for inactivating week schedule.
DAY SCHEDULE
Main index > Unit > Operating functions > Time switch program > Schedule
Parameter
Value
Function
Current value
–
Switching according to schedule when current day of the week is the
same as the switching day.
Day schedule
– Passive
– Active
Status for current week or exception day:
– Current day of the week (system day) is not the same as switching day.
– Current day of the week (system day) is the same as switching day.
Time-1
Special case: This time may not be changed; it must always be 00:00.
Value-1
Switching command for Time-1.
Time-2
Switching time 2. *: * ---> Time disabled.
Value-2...Value-6
Analogue value 1.
Time-3 ... Time-6
Analogue time 2.
Note!
TIME SWITCH PROGRAM
11.2
11.3
11.4
1270466_utg3_HERU_400_1200_eng.indd 48
2020-10-28 11:59:48
1270466_utg3_HERU_400_1200_eng.pdf 48
2020-10-28 12:04:21