3.6.3. Fitting hot water cylinder temperature sensor (PTV-E only)
The PTV – E has a temperature sensor supplied with the boiler which must be fitted to the domestic hot water
cylinder as this ensures a correct reading of the secondary (DHW) temperature.
Use twin core cable of diameter 0.6mm2 to 0.75
mm2. The cable runs from the boiler to the hot
water cylinder and the probe should be inserted
approximately 30% of the way up the cylinder and at
least in the top half of the area covered by a heating
coil. The probe must be touching the cylinder wall
and held in place using the cylinder insulation.
Alternatively a thermostat pocket can be used if
available and in the correct position.
Water Cylinder temperature sensor
Water cylinder temperature sensor connection point
on boiler's connection plate
3.6.4. Fitting pump connections and expansion vessel (RS – E only)
Termo RS – E requires expansion vessel and pump(s) to be connected to the heating circuit according to diagram
on page 6. Circulation pumps for central heating and hot water should be connected to connections plate
according to diagrams in Appendix 1.
Termo Plus and PTV boilers are supplied with pumps and expansion vessel factory fitted and pumps wired to the
connections plate.