RECOMMENDATION
- Mains cable (1) for wall socket/wall box should be hidden under one of the channels in the bottom
of the product, as shown.
-
For products with ≤ 2kW capacity, a
> 10A fuse / > 1.5# wire should be used*.
For products with ≤ 3kW capacity, a
> 15A fuse / > 2.5# wire should be used (230V).
3.6.4 Fitting instructions
3.6.5 Fitting recommendation
!
WARNING
!
The product should be filled with water before the power is switched on.
!
Fixed electric fittings should be used for installation in new homes or when changing an existing
electrical setup in accordance with regulations. A mains cable with plug for wall socket can be
used when replacing the product without changing the electrical setup.
!
The mains cable should withstand 90°C. A strain reliever must be fitted (supplied).
!
CAUTION
!
The product must have a clearance for servicing of 40 cm in front of the cover / 10 cm
over the top connection.
!
If the mains cable is damaged, it must be replaced with cable of a quality that meets the
requirements of the installation. The cable must be replaced by a qualified electrician.