OSAKA- CI 49 Operating instructions. PAGE 5 

- U KEY OPERATING MODE: This parameter permits to 

decide  the operating mode of the frontal U key and the 
possibilities are: 
0 = Key disable 
1 = RESET 
 

6- PROBLEMS, MAINTENANCE AND WARRANTY 

 
6.1 – CLEANING 

It’s recommended to clean the instrument only with a cloth 
welted  with water or with a detergent neither abrasive nor 
containing solvents. 

 
6.2 – WARRANTY AND REPAIRS 

The instrument is under warranty against construction vices or 
defected material, noticed within 12 months from delivery date. 
The  warranty is limited to the repairs or to the substitution of 
the  instrument. The eventual opening of the housing, the 
violation of  the instrument or the wrong use and installation of 
the product means the automatic decay of the warranty. 
In case of defected instrument, noticed in warranty period or 
out of  warranty, do contact our sales department to obtain the 
shipment authorisation. 
The defected product must be shipped to  OSAKA with the 
detailed description of the failures found and without any fees 
or charge for OSAKA, safe different agreements. 
 

7 - TECHNICAL DATA 

 
7.1 – ELECTRICAL DATA 

Power supply: 12 VDC/VAC, 24, 115, 230 VAC +/- 10% 
Frequency AC: 50/60 Hz 
Power consumption: 3 VA approx. 
Input/s: 2 digital inputs for Count (CNT) and Reset (RES) for 
voltage-free contacts or voltage signals (the same voltage 
supply value). 
Output/s: Up to 2 outputs. Relay SPDT (8 A-AC1, 3 A-AC3 / 
250 VAC); or in tension to drive SSR (12VDC/15 mA). 
Electrical life for relay outputs: 100000 operat. 
Voltage inputs absorption: 1 mA Max. 
Installation category: II 
Protection class against electric shock: Class II for Front panel 
Insulation: Reinforced insulation between the low voltage 
section  (supply and relay  outputs) and the front panel; 
Reinforced insulation  between the low voltage section (supply 
and relay outputs) and the  extra low voltage section (inputs, 
SSR outputs); Reinforced  insulation between the extra low 
voltage section (SSR outputs) and voltage inputs. 
 

7.2 – MECHANICAL DATA 

Housing: Self-extinguishing plastic, UL 94 V0 
Dimensions: 48 x 48 mm DIN, depth 98 mm 
Weight: 200 g approx. 
Mounting: Flush in panel in 45 x 45 mm hole 
Connections: 2 x 1 mm 

screw terminals block 

Degree of front panel protection : IP 54 mounted in panel with 
gasket 
Pollution situation: 2 
Operating temperature: 0 ... 50 °C 
Operating humidity: 30 ... 95 RH% without condensation 
Storage temperature: -10 ... +60 °C 
 

7.3 – MECHANICAL DIMENSIONS, PANEL CUT OUT AND 
FIXING DEVICE [mm] 

 

 

 

 
7.4 – FUNCTIONAL DATA 

Outputs operating mode: 3 modes for OUT 1: RESTART, 
RESTART-LAP, COUNT.  4 modes for OUT 2: like OUT1, ON 
during count, like OUT1 with set  C2 absolute or relative in 
advance. 
Measurement range: 9999 Max. 
Max counting input frequency: programmable from 2Hz up 
1000 Hz 
RES Input delay: 15 m sec. Max. 
Display: 4 Digit Red h 12 mm 
Compliance: ECC directive EMC 89/336 (EN 61326), ECC 
directive LV 73/23 and 93/68 (EN 61010-1) 
 

7.5 – INSTRUMENT CODE 
 
 

CI    

=   formato (48x48), Ip65
=   formato (72x72),    

Ip65

= 230 Vac

=     24 Vac

=     2 relés

= 110 Vac

=     12 Vac/d c

=     a la cone xión 

=     standard

=    salid a   SSR+ Relé

-

C

SR

4 9

73