6. Installation and connection

 6.1. Installation preparation

Prior to installing the unit the following shall be done:

Check the signal level of the base station at the place of installation. The connection must
be robust; the voice on the phone shall have no echo or distortions;

Select location for the unit installation (on the Control Panel housing or another place). If
the unit and the Control Panel will be placed separately, the distance between them should
be less than 3m;

For the installation on the Control Panel's housing, drill 7-8 mm hole in the Control Panel
housing to insert external wires, according to Figure 1 – over the corresponding hole on the
unit housing;

Configure the Control Panel according to the manufacturer’s instruction (see section 6.3);

Configure Lun-9C unit (see section 6.4).

 6.2. Unit installation

The unit shall be installed as follows:

1. Power off the Control Panel.
2. Disconnect the battery from the Control Panel.
3. Insert the wires to the unit inputs and power circuits. The input wires must be double-

isolated.

4. Fix the housing base on the Control panel housing using the double adhesive tape 3M 4026,

which is already installed on the back side of the unit housing. If it is not, place it on the
housing using the supply package. To do this, cut the tape in two (50 mm), take off the
protecting film on the one side of each piece of the tape and adhere it on the previously
degreasing back side of the unit housing (see Figure 1). Degrease the places where the tape
is adjacent to the Control Panel housing, take of the protecting film (from both sides) and
install the unit. The recommended temperature for adhering the tape is +20 to +40 °C.

5. Connect the wires to the terminals according to Figures 3 or 4 (it depends of the unit mode

selected).

6. Insert SIM card in the holder.
7. Connect the power wires. It is recommended to connect the power supply terminals to the

Control   Panel's   output   for   peripheral   devices.  If   the   Control   Panel   hasn't   such   output,
connect the board power supply terminals to the external 12V battery with the own charger.

8. Connect the battery to the Control panel.
9. Power on the Control Panel. The power supply of the unit must be on automatically.

 6.3. Control Panel configuration recommendations

When configuring the Control Panel communicator follow the following recommendations:

Dial up –tone;

Transmission protocol – tone ContactID; if not supported – pulse one 20bps speed;

Transmission attempts number – 10 (max);

Repeat time – 1 minute (min);

АДМА.425938.003 РЭ

Rev. en_11

8

Summary of Contents for Lun-9C

Page 1: ...modes and conditions therefore meeting the requirements of this document is mandatory Lun 9C Fire and Intrusion Alarm Communicator Operation Manual ORTUS Group 2016 Product Compatibility Table Contro...

Page 2: ...LED indicators 7 6 Installation and connection 8 6 1 Installation preparation 8 6 2 Unit installation 8 6 3 Control Panel configuration recommendations 8 6 4 Unit configuration recommendations 9 7 Rem...

Page 3: ...or covert video or audio recording 2 Safety Precautions Only the employees familiar with the Control Panel arrangement instructed on the safety arrangements and having the permit to work with electric...

Page 4: ...4 Appearance and functions of unit terminals The appearance of the unit is shown in Figure 1 the appearance of the board is shown in Figure 2 425938 003 Rev en_11 4 Figure 1 Unit appearance...

Page 5: ...10 14 V GND Common contact Communication protocols tone Contact ID pulse with the speed of 20 bit sec Terminal resistors of 4 7 kOhm are used see the connection diagrams in Figures 3 4 Load capacity 1...

Page 6: ...t itself are used 5 1 Unit operation modes The unit can operate in one of the following two modes 1 Fire mode Used as a Fire Alarm and Malfunction Warning Unit according to EN 54 21 The connection dia...

Page 7: ...ansmitted to CMS lit off after Reset in the Control Panel Not lit and not flashing normal state no alarms Mode indicator operation modes Short flashes in every 4 seconds waiting state message buffer i...

Page 8: ...nstalled on the back side of the unit housing If it is not place it on the housing using the supply package To do this cut the tape in two 50 mm take off the protecting film on the one side of each pi...

Page 9: ...e at the temperature of 5 C to 40 C and the relative humidity of 5 up to 85 10 Storage Storage temperature shall be of 50 C 40 C at the relative humidity of 5 up to 98 During handling operations trans...

Page 10: ...is mandatory Failure to comply with this requirement can lead to the unit malfunction and warranty disclaimer Figure 3 Diagram of connection of the unit to the Control Panel Option 1 Figure 4 Diagram...

Page 11: ...Lun 9C PCB for the voltage level matching This module is placed to XP2 connector see Figure 5 Then you connect Strelets Control Panel to the unit see Figure 6 Figure 5 MC 1 interface module installati...

Page 12: ...alfunction of the Equipment 8 Manufacturer shall not be liable under the Warranty if the test and or analysis conducted by the Manufacturer shows that the product has no claimed defect or it that this...

Reviews: