4.5. Adjusting
After installation, the detector should be configured in the following order:
1. Remove both power sources;
2. Set the DIP-switches
#1
,
#2
,
#3
to
OFF
;
3. Install detector power sources –
BACKUP
first then
MAIN
;
4. Assess the level of acoustic noise at the installation place by the indicator glowing green
(no interference if there is no glow). If interference is present, their source should be
eliminated;
5. Set the switches
#1
,
#2
,
#3
to
ON
. The indicator starts flashing green 1 time per second;
6. Close the detector cover;
7. Apply a few blows to the protected glass (in the part farthest from the detector) with a
steel ball with a diameter of ~21mm suspended on a thread 35 cm long, deflecting it to
the angle indicated in Table 2.
Table 2. Ball deflection angle for detector setup
Ball deflection
angle
Glass thickness, mm
<3
3…4
4…5
5…6
6…7
>7
Ordinary glass
30
35
40
45
50
55
Tempered and
laminated glass
45
50
55
60
65
70
8. If the alarm is not generated, then the detector sensitivity should be increased with the
switches
#1
,
#2
according to Table 3.
Table 3. Sensitivity setting
Switch position
Sensitivity
#1 (SENS1)
#2 (SENS2)
ON
OFF
-6dB
OFF
ON
-12dB
ON
ON
-18dB
OFF
OFF
Maximum sensitivity
9. When setting is complete, set switch
#3
(
TEST
) to
OFF
.
5. Maintenance
The product work should be checked annually.
6. Operating conditions
1. Detector is designed for continuous operation.
2. Detector shall be used at the temperature of –20°С to +55°С and relative humidity of 5% to
85%.
3. If the transportation conditions differ from the operating conditions, then the detector must
be kept in the operating conditions for 2…6 hours before switching on.
GBD-R
Version en_2