In addition, the detector transmits periodic test signals to the receiver to confirm its operabil-
ity. When the test signals stop, the control panel generates the
detector communication lost
event.
The detector is protected from false alarms during shocks, vibrations and acoustic noises that
do not destroy the protected glass surface.
When the communication loss with the receiver, the detector continues to search it. Therefore,
when you turn off the receiver or control panel for a long time, it is recommended to remove the
detector’s batteries.
4.1. Modes Indication
The detector modes displays by multicolored LED:
Norm
– light off;
Noise
– glows green during interference;
Alarm
– flashing red once every 3 seconds. This flashing will operate up to 10 minutes
after the detector’s cover is closed then flashing stops to conserve the battery;
Binding
– blinking green while waiting for a signal from the Lun-R receiver to register in
the control panel memory;
Bound
– when the binding is completed successfully – turning on red for 2…3 seconds;
Settings
– flashing green every one second – while the DIP-switch #3 is on.
4.2. Binding
A new detector must be bound to the control panel in order to successfully transmit its com-
mands to the receiver.
To register a detector, do the following:
1. In the control panel configuration, pre-set the required number of radiozones, their type,
group membership and other parameters;
2. Turn on the control panel in the operating mode and switch to the desired control
panel’s group;
3. Switch the control panel to the wireless detectors binding mode (see the corresponding
control panel programming manual);
4. Install the batteries to the detector observing polarity –
BACKUP
first, then the
MAIN
;
5. Switch the detector to the binding mode by short-circuit the
RESET
contacts for 2…3 sec-
onds (until the blinking green – the signal "
Binding
");
6. Binding will processed automatically and, if successful, ends by turning on the red LED
for 2…3 seconds (signal "
Bound
").
The detector waits 70 seconds for binding. To reinitialize the binding process, briefly close the
RESET
contacts again.
GBD-R
Version en_2
5