INSTALLATION GUIDE
Humidity & Fan Control Sensor
MODEL
WM-DWHS
Instruction Manual
1-888-543-6473
1-888-541-6474
13376 Comber Way
Surrey BC V3W 5V9
[email protected]
www.ortechindustries.com
375 Admiral Blvd
Missis
s
auga
,
ON L5T 2N1
Troubleshooting
The buttons do not react:
Check if the panel is installed properly
Press the fan button, if the relay does not work and the
indicator light does not flash:
Turn OFF power to the circuit then check wire connections
If the relay operates normally but the load will not turn on:
Check the load
The fan keeps working under humidity setting point:
When it can be turned off by a manual button, check if the sensor
is broken or not
Function Setting
1. START program mode
Press and hold the fan button for 5 seconds. Its red and white LED
will stay on. The sensor is now in Program Setting Mode. The LED
flash time will show the current function, flashing 1/2/3 times
show the corresponding function 1/2/3. Flashing once means
function 1 "Low Humidity".
2. CHANGE program function
Press the button 1/2/3 times to enter a function to change. The
fan LED flashes with each press, then press and hold the button
for 5 seconds, the LED flashes 3 times, the new setting is saved
and then sensor will exit the setting mode.
3. During the Program Setting Mode, after pressing and holding
button for 5 seconds, when the LED looping 10 times and no
further action or the setting is saved, the LED flashes 3 times and
then the sensor will exit the setting mode (when exit the setting
mode, the load will be turned off at the same time).
F
an LED
Fan: BI-Colour (red or white LED)
Bi-colour light is just for display humidity use only. When the
environment humidity is higher than the set point, red LED will be on.
When the humidity is lower than the set point, white LED will be on.
When power on, the red/white LED will flash once.