IG-245-EN version 05; 13/02/2020
6
Description and main characteristics
General Instructions
mb
.m
1.1.1. Medium voltage switchgear
The medium voltage switchgear, in compliance with
Standard IEC 62271-200, includes a rust-protected
independent metal outer enclosure with front access.
The medium voltage electrical equipment that can be
incorporated is as follows:
•
cgmcosmos
(IEC), 24 kV - 400/630 A system, technical
specifi cations in accordance with general instructions
document
IG-078
.
•
cgmcosmos
(IEEE), 27 kV - 600 A system, technical
specifi cations in accordance with general instructions
document
IG-182
.
•
cgm
.3 (IEC), 40.5 kV - 400/630 A system, technical
specifi cations in accordance with general instructions
document
IG-136
.
•
cgm
.3
(IEEE),
38 kV - 600 A
system,
technical
specifi cations in accordance with general instructions
document
IG-183
.
•
ga
/
gae
system (IEC), 24
kV - 630
A, technical
specifi cations in accordance with general instructions
documents
OI-122492291
-ga-Blokschaltanlage-EN
and
OI-21023619-09
GA-2K1LSF-10.
Possible configurations:
There are two variants of
mb
.m:
•
mb
.m-3f: allows the installation of up to three
switchgear functional units, in accordance with the
following confi gurations:
-
cgmcosmos
-lv,
cgmcosmos
-3l,
cgmcosmos
-2lp,
cgmcosmos
-2lv.
-
cgm
.3-lv,
cgm
.3-3l,
cgm
.3-2lp,
cgm
.3-2lv.
-
ga
-3k,
ga
-2k1ts,
ga
-2k1lsf; 1400 mm high, variants
1 and 2.
•
mb
.m-4f: allows the installation of up to four switchgear
functional units, in accordance with the following
confi gurations:
-
cgmcosmos
-lv,
cgmcosmos
-3l,
cgmcosmos
-4l,
cgmcosmos
-3lv.
-
cgm
.3-lv,
cgm
.3-3lp,
cgm
.3-4l,
cgm
.3-3lv.
-
ga
-4k,
ga
-3k1ts,
ga
-3k1lsf; 1400 mm high, variants
1 and 2.
The access doors to the electrical switchgear are double leaf
with eff ective opening of:
•
mb
.m-3f: 1442 x 1840 mm (high x wide).
•
mb
.m-4f: 2000 x 1840 mm (high x wide).
The doors can be folded to 90º and 180º, with two anchorage
points and a fastening pin for the open positions to prevent
them from being unexpectedly closed.
Furthermore, the medium voltage switchgear can be
ordered with a locking device for the medium voltage cable
input in the bottom part of the enclosure. It has up to three
one-core cable inputs, with a maximum diameter of 50 mm.
For other types of cables, please contact
Ormazabal
.