Recommended sequence of operations
5. Recommended sequence of operations
Before carrying out any operation when voltage is
present, we recommend checking the SF
6
gas pressure,
using the manometer.
5.1. Checking the gas pressure
Each tank has a pressure gas with temperature
compensation for checking the gas pressure, which can
easily be seen from outside the cubicle. The pressure gauge
scale is divided into different colours: red and green. For
safe operation, the needle must be in the green zone of the
corresponding temperature band.
Main characteristics:
• Two normally open (NO) voltage-free contacts calibrated
at the same level.
• Accuracy class: + 20 °C - 1%
- 30 °C to 60 °C - 2.5 %
• Temperature range: - 30 °C to + 60 °C
Figure 5.1.
Pressure gauge with temperature compensation