Recommended sequence of operations
General instructions
cgm
.3 system: medium voltage SF
6
gas-insulated
cubicles up to 38 kV according to IEEE and CSA standards
5.
Close the circuit-breaker by pressing button “I”, and
check the status indicator.
Figure 5.42.
Grounding switch open
Manual driving mechanism (AV):
Charge springs,
operating the charge lever (see Section “
.3-v”), until the spring is shown as
tight. Once the spring has been tightened, close the switch
by pressing the close button; then check the status indicator
and whether voltage is present in the
ekor
.vpis unit.
Motor driving mechanism (AMV):
Close the switch by
pressing the closing button; then check the status indicator
and whether voltage is present in the
ekor
.vpis unit.