Ormandy SCP PLUS 3000 Technical Manual Download Page 4

 

 

 

 

2.  TECNICAL SPECIFICATIONS 

 

 

 

 

2.1 DATA TABLE 

 

 

 

SCP Plus Model 

3000 

3500 

4000 

5000 

6000 

7000 

Output (kW) 

3000 

3500 

4100 

5000 

6000 

7000 

Dimensions & weight

 

A   

2460 

2460 

2700 

2700 

2820 

2820 

B   

2135 

2135 

2345 

2345 

2495 

2495 

3879 

4379 

4379 

4879 

5379 

5879 

2210 

2210 

2420 

2420 

2570 

2570 

1300 

1300 

1400 

1400 

1600 

1600 

3430 

3930 

3930 

4430 

4930 

5430 

1012 

1012 

1012 

1262 

1262 

1262 

1500 

2000 

2000 

2200 

2700 

3200 

1230 

1230 

1335 

1335 

1410 

1410 

1230 

1230 

1335 

1335 

1410 

1410 

Approx. dry weight  (kg) 

6300 

6950 

8200 

8970 

11280 

12160 

Efficiency based on net CV

 

Efficiency (%) @ 100% load  

92.0 

92.0 

92.0 

92.0 

92.0 

92.0 

Efficiency (%) @ 30% load 

94.0 

94.0 

94.0 

94.0 

94.0 

94.0 

Gas flow rate  G20  (m

³

/h) 

345 

403 

472 

575 

690 

805 

Combustion and flue data

 

Flue Gas Volume  (m

³

/min) 

130.5 

152.2 

178.3 

217.4 

260.9 

304.4 

Approx Flue Gas Temp. (ºC) 

181 

181 

182 

181 

181 

181 

Comb. Chamber Resistance  (mbar) 

13.5 

18.0 

11.7 

14.0 

12.0 

14.0 

Water system

 

Hydraulic Resistance (11k) (mbar ) 

64.2 

86.9 

120.1 

73.8 

105.9 

144.0 

Hydraulic Resistance (20k) (mbar ) 

19.4 

26.3 

36.4 

22.3 

32.0 

43.6 



 



 



 



  



k

  

 

 

 

16.2 

18.9 

21.7 

27.1 

32.5 

37.9 



 



 



 



  



k

  

 

 

 

8.9 

10.4 

11.9 

14.9 

17.9 

20.8 

Water content  (l) 

4496 

5212 

6125 

7335 

9088 

10066 

Connections

 

Flue connection size (mm) 

550 

550 

600 

600 

700 

700 

Flow & Return flanged connection 
(mm) 

200 

200 

200 

250 

250 

250 

Drain connection size  (mm) 

40 

40 

40 

40 

40 

40 

Safety valve size 

50 

50 

50 

65 

65 

65 

 

 

 
 
 

Summary of Contents for SCP PLUS 3000

Page 1: ...TECHNICAL MANUAL The above picture is only for reference SCP PLUS THREE PASS WET BACK HOT WATER BOILER ...

Page 2: ...ions 3 2 2 Drawing 4 3 ACCESSORIES 5 3 1 THERMOSTATS 5 3 2 MANOMETER 5 3 3 THERMOMETER 5 4 INSTALLATION 6 4 1 BURNER 6 5 STARTING 7 5 1 PRELIMINARY CHECKS 7 5 2 WATER TREATMENT 7 5 3 FILLING THE SYSTEM 7 6 OPERATION 8 6 1 OPERATION CHECKS 8 6 2 CLEANING AND SERVICING 9 ...

Page 3: ...ion code Rated thermal output in kW Types of fuels that can be used Max operating pressure IMPORTANT This boiler has been designed to heat hot water at a temperature inferior to the boiling temperature at atmospheric pressure and must be connected to a heating plant and or a domestic hot water plant within the limits of its performance and output ...

Page 4: ...load 92 0 92 0 92 0 92 0 92 0 92 0 Efficiency 30 load 94 0 94 0 94 0 94 0 94 0 94 0 Gas flow rate G20 m h 345 403 472 575 690 805 Combustion and flue data Flue Gas Volume m min 130 5 152 2 178 3 217 4 260 9 304 4 Approx Flue Gas Temp ºC 181 181 182 181 181 181 Comb Chamber Resistance mbar 13 5 18 0 11 7 14 0 12 0 14 0 Water system Hydraulic Resistance 11k mbar 64 2 86 9 120 1 73 8 105 9 144 0 Hydr...

Page 5: ... safety pressure switch not supplied N1 Flow N2 Return N3 Fitting for instruments N4 System filling drainage N5 Connections for safety valves N6 Bulb wells N8 Inspection well N11 Fitting for level minimum probe SCP PLUS 3000 7000 NOTE drawing legend and data refer to standard models For specific models please refer to the provided accessory drawing ...

Page 6: ...te the second flame of the two stage burner The safety thermostat locks the burner at a fixed temperature value and sends out an alarm signal Restarting occurs only after the cause of the alarm has been removed and the system has be reset by operating the reset button on the switchboard 3 2 PRESSURE GAUGE The pressure gauge is Bourdon type consisting of a flat elliptical section metal tube bent to...

Page 7: ...Check that the boiler is fired by the correct type of fuel d Check that the fuel supply pressure is within the values specified on the burner rating plate e Check that the fuel supply system is sized for the maximum flow rate necessary for the boiler and that it is provided with all control and safety devices provided for by the regulations referred to above f Check that the boiler room vents are ...

Page 8: ...evel is to eliminate areas that overheat Scale creates an insulating layer which reduces the thermal transfer of the generator affecting system efficiency This means that the heat produced by burning the fuel is not fully exploited and is lost to the flue Scale diagram Key fuel not used mm mm of scale Corrosion on the water side Corrosion of the metal surfaces of the boiler on the water side is du...

Page 9: ...rature CO Gas 10 190 C 0 20 ppm Gas oil 13 195 C 10 80 ppm Heavy oil 13 5 200 C 50 150 ppm A diagram is provided in which the system efficiency is obtained according to the flue gas temperature the ambient temperature and the percentage of carbon dioxide CO2 Dispersions through the boiler casings are not considered Example Fuel used GAS OIL CO2 13 Ambient temperature 20 C Efficiency 91 4 Key Tf Fl...

Page 10: ... box while the burner is working Always wait few minutes after the burned has been switched off until the insulating parts are cooler 6 2 CLEANING AND SERVICING Close fuel supply and disconnect the electrical mains before starting any cleaning and servicing operations As economic running depends on cleaning of the exchange surfaces and regulation of the burner the following operations should be pe...

Page 11: ...10 ...

Page 12: ...t Street Halifax HX1 4DB Tel 01422 355651 Fax 01422 359636 The data reported are indicative only and are not binding Our company reserves the right to introduce alterations at any time as it deems fit and proper for the development of the product ...

Reviews: