6  STARTING 

 
IMPORTANT:   before  starting  insert  the  flue  gas  baffles  completely  in  the  flue  gas  pipes,  pushing 
them in by at least 100 mm.

 

6.1  PRELIMINARY CHECKS 

Before starting the boiler, make sure that: 

The number plate data corresponds to the electrical, water and liquid or gas fuel supply data; 

The burner rating is compatible with that of the boiler; 

The burner and boiler instructions are available in the boiler room; 

The chimney operates correctly; 

The ventilation openings are adequately dimensioned and free of all obstacles; 

The  door,  the combustion chamber and the burner plate are closed so that the boiler is gas tight at all 
positions; 

The system has been filled with water and that any air locks have been eliminated; 

There is frost protection; 

The water circulation pumps operate correctly; 

The  expansion  tank  and  the  safety  valve(s)  are  correctly  connected  with  no  valves  between  boiler  and 
valves. 

 

Check the electrical system and that the thermostats are operating. 

6.2  WATER TREATMENT 

 
If  the  boiler  is  to  be  installed  in  an  existing  system  where  there  could  be  frequent  losses  from  the 
system or if the hardness of the water is greater than 10 F, it will be necessary to use a filter and a 
softener for system water and control the pH above 8-9. 

The most common phenomena in heating systems are: 

Furring (calcareous deposits of Calcium Carbonate) 

Furring impedes heat exchange between the flue gases and the water, thereby increasing the tempera-
ture of parts exposed to the flame and reducing considerably the boiler life. Furring concentrates where 
the  boiler  wall  temperature  is  higher,  and  the  best  defence  against  this phenomenon is a boiler design 
that eliminates high temperature spots. 
Furring  represents  an  insulation  layer  that  decreases  heat  exchange,  penalising  boiler  efficiency.  This 
means that a large part of the combustion heat is not transferred to the water, but leaves the system via 
the chimney. 
 

Calcium Carbonate Diagram

  

 

Legend 
%

  

% unused fuel 

mm 

mm furring 

 

Water-side corrosion  

Corrosion  of  metallic  boiler  surfaces, 
waterside,  is  due  to  Iron  dissolving  to 
form  ions  (Fe+).  In  this  process,  the 
presence  of  any  dissolved  gas  plays a 
major  role,  in  particular  oxygen  and 
carbon  dioxide.  Often  there  are  corro-
sion  phenomena  with  softened  and 
demineralised  water,  which  are  by  their  nature  aggressive  to  iron  (acid  water,  that  is    with  pH  <  7):  in 
these  cases  though  clearly  there  will  be no furring, corrosion remains a risk and it will be necessary to 
condition the feed water with corrosion inhibitors. 

6.3  FILLING THE SYSTEM 

The  water  must  enter  the  system  as  slowly  as  possible,  and  in  proportion  to  the  rate  of air purge from the 
components involved. In the case of a system with a closed expansion tank, water is injected until the pres-
sure gauge reaches the static pressure for the tank. Then proceed to heat the water to the maximum allowed 
plant  temperature,  but  not  higher  than  90°C.  During  this  operation,  the  air  in  the  system  purges  from  the 
automatic or manual air separators fitted to the system. On completion of the air purge, bring the pressure to 
the set value and close the manual and/or automatic water supply valve. 

Summary of Contents for Norland

Page 1: ...TECHNICAL MANUAL NORLAND CONDENSING BOILER WITH BURNER LOW NOx STAINLESS STEEL CONDENSING BOILERS ...

Page 2: ...0 120 9 4 8 INVERTING THE DOOR APERTURE MOD 160 860 9 4 9 PRESSURISED BOILER CONNECTION 10 4 10 WIRING DIAGRAM 10 5 FITTING THE BOILER CASING 11 5 1 BOILER BODY INSULATION 11 5 2 BOILER CASING MOD 90 120 11 5 3 BOILER CASING MOD 160 270 12 5 4 BOILER COVERING MOD 350 860 13 6 STARTING 14 6 1 PRELIMINARY CHECKS 14 6 2 WATER TREATMENT 14 6 3 FILLING THE SYSTEM 14 7 OPERATION 15 7 1 OPERATION CHECKS ...

Page 3: ...s much as possible the formation of Nitrogen Oxides NOx that form when the flame remains at high temperature in the combustion chamber for long periods The Norland boilers place no limit on the return water temperature and reach the highest performance when used with floor panel heating systems in which the return temperature is lower than 58C At higher tempera tures condensation does not occur an...

Page 4: ...e control panel should be checked for efficiency The guarantee shall be valid only upon compliance with the instruction given in this manual Our boilers have been built and tested in observance of EEC requirements and consequently CE marked EEC direc tives are as follows Directive on Gas 90 396 EEC Directive on Output 92 42 EEC Directive on Electromagnetic Compatibility 89 336 EEC Directive on Low...

Page 5: ...89 569 589 569 H10 432 432 432 562 562 562 524 524 524 524 524 L 939 966 966 1063 1063 1063 1201 1201 1201 1201 1201 L1 756 756 756 853 853 853 991 991 991 991 991 L2 710 710 710 814 814 814 932 932 932 932 932 L6 150 150 150 200 200 200 200 200 P 990 1330 1330 1550 1550 1801 1817 2331 2331 2331 2331 P1 881 1221 1221 1296 1296 1546 1577 2092 2092 2092 2092 P2 670 1010 1010 1004 1004 1254 1205 1720...

Page 6: ...KEY N1 Boiler flow N2 Medium temperature return N3 Fitting for Instruments N4 System filling drainage N5 Safety valve s fitting N6 Bulbs wells N7 Boiler condensation drain N8 Inspection well N9 Low temperature return T Inspection plugs ...

Page 7: ...NORLAND 6 Mod 340 860 ...

Page 8: ...UNI 9615 WARNING The flue gas temperatures produced by MONOLITE boilers are considerably lower than in the case of non condensing boilers and have therefore very high relative humidity For these reasons the chim ney must be completely watertight must withstand corrosion attack by acid condensate and must be adequately heat insulated to guarantee sufficient draught 4 2 1 Condensate drain Connect co...

Page 9: ... thermostats TR1 TR2 have an operating range from 0 to 90 and can be set by the user by means of the front dial Safety limit thermostats TS has a fixed setting of 100 0 6 C and can be manually reset For correct installation refer to the boiler casing assembly instructions 4 6 STARTING Open the gas tap check if there is any gas leakage Switch on the burner and heating pump on the control panel At t...

Page 10: ...4 8 INVERTING THE DOOR APERTURE mod 160 860 If the door is to be opened to the opposite side act as follows 1 Switch the outside nut or bush of one hinge with the diametrically opposite closure bush then at the hinge side fasten the cone to the door with the inside nut 2 Repeat the operation for the other hinge 3 For any adjustment needed act on the specific hinge nuts ...

Page 11: ...as connections are perfectly gas tight h check that the boiler room ventilation openings are dimensioned to guarantee an air flow as foreseen by applicable regulations and in any case sufficient for perfect combustion i check that the gas pipes are not used as a ground earth for electrical devices If the boiler will not be used for some time close the fuel supply IMPORTANT check that the spaces be...

Page 12: ...ontrol panel connection cables passing through the aperture for the wiring harness please refer to the control panel diagram and to the standard plugs connection kit Unwind the thermostat capillaries fit the control panel 3 to the side RH or LH fastening with the screw then insert the bulbs in the pocket Hook the upper rear panel 4 to the sides Fasten the support bracket 5 to the frame base L prof...

Page 13: ...ss please refer to the control panel diagram and to the standard plugs connection kit Unwind the thermostat capillaries fit the control panel to the side fastening with the screw then insert the bulbs in the pocket Fit the upper panels 4S and 4D Mount the panel 5 attach the support bracket 6 to the corner of the frame base position the panel 7D and then the panel 7S with fairlead attached to its s...

Page 14: ...xisting opening for the wiring harness please refer to the control panel diagram and to the standard plugs connection kit Unwind the thermostat capillaries attach the control panel 3 to the side with a screw then insert the bulbs into the shaft Mount the upper panels 4P 4D and 4S with screws and plug the holes with the caps Mount the panel 5 attach the support bracket 6 to the frame base position ...

Page 15: ...ts exposed to the flame and reducing considerably the boiler life Furring concentrates where the boiler wall temperature is higher and the best defence against this phenomenon is a boiler design that eliminates high temperature spots Furring represents an insulation layer that decreases heat exchange penalising boiler efficiency This means that a large part of the combustion heat is not transferre...

Page 16: ...ler WARNING during long stoppages in winter and in order to avoid frost damage drain both the sanitary wa ter and the heating system water drainage of the latter can be avoided by adding antifreeze Boiler with water heater 7 4 PERIODICAL USER CHECKS Check periodically that there is no air in the heating system and if necessary open the blow off valve at the top of the boiler Periodically check the...

Page 17: ......

Page 18: ...93120032 Ed 10 05 08 10 St 10 05 08 ...

Reviews: