28
Troubleshooting
Alarm Types and Product Response Chart
Alarm Types and Product Response Chart
■
Alarm List
Alarm
number
Name
Actions in
response to
alarms
Operation
signal
Alarm
signal
Display
Restore
C00
500-hour filter use caution alarm
Running
○
×
Alternate
displays
Manual
E01
Compressor motor protector
All stopped
×
○
Alternate
displays
Manual
E02
High pressure switch
All stopped
×
○
Alternate
displays
Manual
E04
Compressor intake temperature sensor
All stopped
×
○
Alternate
displays
Manual
C07
Liquid temperature limit alarm
Running
○
○
Alternate
displays
Auto
C08
Compressor stop less than 3 minutes
Running
○
×
Alternate
displays
Auto
E09
Power phase loss(RKS500,750F)
All stopped
×
○
Blinking
Power-on
E10
Power phase reversal(RKS500,750F)
All stopped
×
○
Blinking
Power-on
E11
Liquid temperature sensor failure
(measured temperature low)
All stopped
×
○
Blinking
Manual
E12
Liquid temperature sensor failure
(measured temperature high)
All stopped
×
○
Blinking
Manual
E13 Memory
error
All stopped
×
○
Blinking
Power-on
E14
Power suspension recovery
All stopped
×
○
Alternate
displays
Manual
E15 Other
error
All stopped
×
○
Blinking
Manual
※
The symbol
○
for signals indicates that a signal is output
,
and the symbol
×
, that no signal is
output.
※
The operating signal and an alarm signal behaviors represent the cases where the respective alarm is
generated by itself.
※
Even with an alarm that sustains a signal generation, the operating signal is suspended if other alarms
are generated in conjunction and the compressor shuts down.
※
"Alternate display" in the Display column indicates that the water temperature measurement and the
alarm number are displayed in turn. "Blinking" indicates that the relevant alarm number blinks.
※
E14 only outputs a signal when "0" (default) is selected for the F1 parameter.