10
Operating Procedures
If Starting Up for the First Time, or After Prolonged Period of Non-Use / Preparation
If Starting Up for the First Time, or After Prolonged Period of Non-Use
Please note the following points before starting the cooler for the first time, or when restarting it
after a long period of non-usage.
1. The pump must not be operated without water. Be sure to supply water before starting the cooler.
2. Check that piping is not leaking.
3. This equipment operates on 3-phase power. If power phases are in reverse, error code “
” will
appear on the display when you start up the power supply (RKS500F,750F). If this occurs, please
change terminal connections on primary side according to “Wiring work” on page 46.
Preparation
■
Checking the Water Level.
1. Make sure that the tank is filled with the water.
Fill the tank, which has a capacity specified on the table below, with the water.
RKS400F-S
RKS500F
RKS750F
Water tank capacity (L)
20 or more
25 or more
35 or more
IMPORTANT
●
If the amount of water is lacking, it could result in a high on / off cycling of the compressor,
which could result in damage to the compressor.
●
Consult with a qualified specialist if the water tank capacity is too low or regarding
construction of an automatic water supply.
■
Priming the Pump
1. Confirm that there is no dirt or other material
clogging the strainer assembly on the water intake
side of the water piping.
2. Wet the pump-priming port gasket with water
beforehand to make it slippery.
3. Slowly add water from the pump-priming port until
the water intake piping and pump are filled.
4. After filling, be sure to hand-tighten the
pump-priming port cap.
IMPORTANT
●
Failure to prime the pump will cause the pump to run dry, preventing water from being chilled,
and it will also result in damage to the pump.
●
Because of the strainer assembly, priming the pump is not required other than when the
product is operated the first time. However, the pump will need to be primed again, as was
done initially, after the water has been drained, after the pipes have been cleaned, or air
entering the water circuit.
●
Priming water only needs to be added so that the water intake piping and pump are filled. Be
careful not to add water too vigorously or all at once. Doing so can cause a siphon effect to
occur, causing the water to be drawn out of the water outlet port, and preventing the water
from collecting where it is needed for priming.
●
Do not loosen the priming water cap while the product is operating. Loosening the cap could
allow air to enter the pump, resulting breakdown due to running dry.
Pump-priming
port cap
Pump-priming
port gasket
Pump-priming
port
Summary of Contents for RKS400F-S