PT SENSORS ENABLED FOR FAN 

 

 

;

Select 

4

 if the temperature of the PT4 sensor will be considered 

for the control of the FAN contact. If 

3

 is chosen, PT4 will NOT be 

considered. 

 

WEEKLY FAN

 

 

 

 

 

 

 

 

 

;

 

 

If 

ON

, the FAN contact will be closed  for 5min each week. This 

function is useful in case the fans connected have not been used 
for  a  long  time,  causing  mechanical  parts  (bearings)  to 
deteriorate, increasing reliability. 

 

BUZZER 

(Optional: see ORDER CODE)

 

 

 

 

 

 

 

;

;

A  high-pitched  tone  will  sound  when  temperature  reaches  the  L1  or  L2 
threshold. This buzzer is installed inside the product. 

 

COMMUNICATION BAUD RATE

 

 

9    6 

 

 (9600); 

 (19200); 

(38400); 

 (57600);  

 

(115200)

 

Baud rate. 

 

ADDRESS 

 

 

 

 

÷

 

Modbus address. 

 

PARITY 

 

 

;

;

;

;

;

Parity and stop bit. 

 

LOCAL/REMOTE CONTROL 

 

 

 

 

 

;

 

 

:

 No setpoint modifications via RS-485, except 

o

C MAX reset. 

:

 Setpoint modifications via RS-485 are allowed. 

 

4-20mA OUTPUT CHANNEL 

(Optional: see ORDER CODE)

 

 

 

;

 

; ;

 

;

 

;

   

Select how the temperatures will be transmitted through the  
4-20mA output. 
 

,  ,   

or

 

:  only the selected PT will be transmitted.  

 

: this option will scan each PT sensor every 5sec. 

 

: hottest PT sensor among the ones connected. 

 

4-20mA OUTPUT LOAD 

(Optional: see ORDER CODE)

 

 

 

100

;

 200

;

 300

;

 400

;

 500 

Select the resistive load [Ω].

 

 

PASSWORD MANAGEMENT 

 

 

;  ;

 

 

(change password)

 

:

 

password not requested to modify the setpoints.

 

: password requested to modify the setpoints.

 

 

:

 

the  user  can  change  the  password  only  if:  password  previously 

inserted and 

USER LOGIN STATUS =

 ON

 
STEP 1: the display will show 

 (new password). 

STEP 2: insert the three new digits. 
To abort press the SET, °C MAX, AUTO button or wait 20sec without pressing 
any key. 
STEP 3: to confirm the new password inserted, press ENTER. The display 
will show 

 

Forgot password? 

Reset to 

factory default password

 (

 

). 

 

STEP 1: disconnect all PT sensors. 
STEP 2: keep simultaneously pressed the UP and DOWN buttons for 2sec. 
The display will show 

. The password is now reset. 

 

USER LOGIN STATUS 

 

 

;

 

 

If  the  password  was  previously  inserted,  the  user  will  remain 
logged in for 5min from the last button pressed.  

 

TEST 

 

 

;

 

;

 

;

 

;

 

;

 

 

The 

;

 

;

 

;

 

 (fault) relay tests work only if the 

relays  are  not  already  excited.  It  lasts  approximately 
5sec. 
 
The 

 Test will simulate the following temperatures 

for 5sec each: 60°C, 180°C, 60°C and 180°C. 
 

 

(buzzer) Test. 

 

4-20mA INDICATOR CALIBRATION ENABLING MENU 

(Optional: see ORDER CODE)

 

 

 

;

 

 

Select 

ON 

to enable the 4mA and the 20mA indicator calibration correction. 

 

CALIBRATION CORRECTION AT 4mA 

(Optional: see 

ORDER CODE)

 

 

 

0.800÷1.200 

Step: 0.001 

4mA will be applied to the output and it will be possible to correct 
the calibration value. 