TR-42 Temperature Protection Relay

 

2

 

Instruction Manual: TR42 GBM 25/02/2021

 

 

5.

 

4-20mA OUTPUT (Optional: see ORDER CODE) 

An indicator can be connected to the 4-20mA output (polarity must be respected). The maximum load impedance is 500 

Ω

. The loop is isolated to ensure 

maximum immunity from disturbances. 
Ratio between output current and temperature: 

I

out = 

(T/15) + 4 [mA]  

where T = °C temperature 

 
Note: It is recommended a shielded and twisted cable, avoiding bends or ring windings, placed away from power cables. 

 
Symbols used in the text:

 

 

               °C 

       PT 

 

 

 

 

 

 

 

 

 

 

Blinking Displays 

Two blinking displays alternate between the options on the first 
row and the second row. 

               °C 

       PT 

 

 

 

 

 

 

Fixed Displays 

Example: 
RANGE: 2; 3; 4

 

 select 

2

, or 

3

, or 

4

 (select among the elements on the list). 

RANGE: 2 ÷ 4

 

 select 

2

, or 

3

, or 

4

 (select any value within the indicated 

parameters). 

 

 

6.

 

ACTUAL VALUES 

Each time the device is powered on, it turns on all LEDs and displays for about 2sec. Once this operation is over, the device begins to function automatically 
in Current Temperature (AUTO) mode. 

 
Current Temperature (AUTO) 

X  X  X 

  Y 

 

XXX: 

Temperature;

 

Y:

 

PT channel

 

Y: 

1; 2; 3 if 

PT SENSORS CONNECTED = 

3

 

Y: 

1; 2; 3; 4 if 

PT SENSORS CONNECTED = 

4

 

Press the SET, °C MAX, AUTO button until the °C MAX LED and the SET 
LED are off. 
The user will see the actual temperature on the °C display and the relative 
PT  sensor  input  on  the  PT  display.  To  manually  scroll  through  the  PT 
channels, press the UP/DOWN buttons. The SET and °C MAX LEDs are 
off. 
 

 

Maximum Temperature (

o

C MAX mode) 

X  X  X 

  Y 

 

XXX: 

Temperature;

 

Y:

 

PT channel

 

Y: 

1; 2; 3 if 

PT SENSORS CONNECTED = 

3

 

Y: 

1; 2; 3; 4 if 

PT SENSORS CONNECTED = 

4

 

Press the SET, °C MAX, AUTO button until the °C MAX LED is on. The user 
will  see  the  maximum  temperature  reached  on  the  °C  display  and  the 
relative PT sensor input on the PT display. To manually scroll through the 
PT channels, press the UP/DOWN buttons. 
By  pressing  ENTER  for  2sec,  the  last  maximum  temperature  of  the 
visualized PT sensor is cleared and the next °C reading will be considered 
the maximum. During this operation, the SET LED is off. 

7.

 

SETPOINTS 

Press the SET, °C MAX, AUTO button until the SET LED is on. 
 

PROGRAMMING MODE (SET mode) 

By pressing SCAN (UP/DOWN buttons), the user can navigate the setpoints. Once on the menu option desired, the display will blink between the new value 
and the value currently set. 
STEP 1: keep the ENTER button pressed for at least 2sec. 
STEP 2: insert the password (three digits) with UP/DOWN and ENTER buttons. If the password is correct, the value to be modified will blink. Otherwise, the 
display will show 

 for a few seconds. 

STEP 3: use the direction buttons to set the new value. 
STEP 4: press ENTER to confirm. 

Note: If the password is disabled or has been previously inserted, STEP 2 will be skipped. 

 

PT SENSORS CONNECTED 

 

 

;

Select the number of PT sensors connected. 

 

ALARM RELAY (L1) 

 

 

÷

 

Step: 1

 

Set the value at which the L1 contact will operate. 
The dropout (reset) value is 2°C less than the setpoint. 
Note: L1 must be < L2. 

 

TRIP RELAY (L2)

 

 

 

 

 

 

 

 

 

÷

 

Step: 1

 

Set the value at which the L2 contact will close. 
The dropout (reset) value is 2°C less than the setpoint. 
Note: L2 must be > L1. 
 

FAN ACTIVATION

 

 

 

 

 

 

 

 

 

;

 

 

If a fan is connected to the FAN contact, select 

ON

 

FAN OFF LEVEL

 

 

 

 

 

 

÷

 

Step: 1

 

FAN will be turned OFF at this temperature.  
Based on the thermal inertia of the system, choose an appropriate 
temperature delta between FAN L and FAN H. 

 

FAN ON LEVEL

 

 

 

 

 

 

 

 

 

÷

 

Step: 1

 

FAN will be turned ON at this temperature. 

 
 
 

Visib

le 

onl

if 

FA

N

 ACT

IVATI

O

N

 = 

ON

 

 