IO data
3 PR
OFINE
52
4-6
Data reading
This section explains the flow that data is read from the driver to the host controller.
There are the following two methods to read data.
•
Use an area of “Read data”
•
Use an area of “Assignable monitor”
When an area of read data is used
z
Area of IO data used
Input (driver
→
host controller)
Byte
Description
30, 31
Read parameter ID_R
32, 33
Read/write status
36 to 39
Read data
Output (host controller
→
driver)
Byte
Description
30, 31
Read parameter ID
z
Flow that data is read from
Host controller
1. Sets the parameter ID to be read from in the
read parameter ID.
3. Checks that the read parameter ID_R has been
the parameter ID having set.
Driver
4. Checks the RD-ERR has been turned OFF.
5. Reads the value of the read data.
2. The data is read every communication cycle.
Read parameter ID
Parameter ID to be read from
1
5
4
3
2
Parameter ID to be read from
Value of parameter ID
to be read from
Communication cycle
Read parameter ID_R
RD-ERR
ON
OFF
ON
OFF
Read data
RD-ERR *
* If the parameter ID out of setting range is set to the read parameter ID, the RD-ERR is turned ON at the same time
when the read parameter ID_R is updated.
Summary of Contents for AlphaStep AZ Series
Page 14: ...1 Introduction 14...
Page 34: ...2 Hardware 34...
Page 118: ...6 Reference materials 118...
Page 119: ...6 Reference materials 119...