Connecting the USB cable (CN4)

Using a USB cable of the following specification, connect a PC in which the 

MEXE02

 has been installed to the CN4 connector.

Specification

USB2.0 (full speed)

Cable

Length: 3 m (9.8 ft.) or less 
Shape: A to micro B

 

y

Connect the driver and PC directly using the USB cable.

 

y

In large electrically noisy environments, use the USB cable with a 
ferrite core or install a ferrite core to the USB cable.

 

„

Noise measures

The electrical noise is of two types: One is a noise to invade into the driver 
from the outside and cause the driver malfunction, and the other is a noise to 
emit from the driver and cause peripheral equipments malfunction.
For the noise that is invaded from the outside, take measures to prevent the 
driver malfunction. It is needed to take adequate measures because signal 
lines are very likely to be affected by the noise.
For the noise that is emitted from the driver, take measures to suppress it.

 

z

Measures against electrical noise

There are the following three methods mainly to take measures against the 
electrical noise.

 

Noise suppression

 

y

When relays or electromagnetic switches are used together with the 
system, use noise filters and CR circuits to suppress surges generated by 
them.

 

y

Cover the driver by a metal plate such as aluminum. This is effective in 
shielding the electrical noise emitted from the driver.

 

Prevention of noise propagation

 

y

Connect a noise filter on the input side of the DC power supply.

 

y

Use shielded twisted pair cables for power lines and signal lines.

 

y

Keep cables as short as possible without coiling and bundling extra lengths.

 

y

Grounding multiple points will increase effect to block electrical noise 
because impedance on the grounding points is decreased. However, 
ground them so that a potential difference does not occur among the 
grounding points.

 

y

To ground a shielded cable, use a metal cable clamp that will maintain 
contact with the entire circumference of the cable. Ground the cable clamp 
near the product.

Cable clamp

Shielded cable

 

Suppression of effect by noise propagation

 

y

Loop the noise propagated cable around a ferrite core. Doing so will 
prevent the propagated noise invades into the driver or emits from the 
driver. The frequency band in which an effect by the ferrite core can be 
seen is generally 1 MHz or more. Check the frequency characteristics of the 
ferrite core used. To increase the effect of noise attenuation by the ferrite 
core, loop the cable a lot.

 

„

Conformity to the EMC Directive

Effective measures must be taken against the EMI that the motor and driver 
may give to adjacent control-system equipment, as well as the EMS of the 
motor and driver itself, in order to prevent a serious functional impediment in 
the machinery. The use of the following installation and wiring methods will 
enable the motor and driver to be compliant with the EMC Directive. Refer to 
p.7 for the applicable standards.
Oriental Motor conducts EMC measurements on its motors and drivers in 
accordance with the ""Example of motor and driver installation and wiring"." 
The user is responsible for ensuring the machine's compliance with the EMC 
Directive, based on the installation and wiring explained below.

 

Connecting the power supply

Use a DC power supply conforming to the EMC Directive. Wire and ground the 
power supply over the shortest possible distance using a shielded cable. Refer 
to "Prevention of noise propagation" for how to ground the shielded cable.

 

How to ground

 

y

The cable used to ground the motor must be as thick and short as possible 
so that no potential difference is generated.

 

y

Choose a large, thick and uniformly conductive surface for the grounding 
point.

 

y

Make sure to ground the Protective Earth Terminal of the motor.

 

Example of motor and driver installation and wiring

The figure shows a wing example when the compact driver and the motor 
(

AZM66

) are used.

Host controller

DC power supply

Grounding

Grounding

Grounding

AC

Grounding

Driver *1

Ferrite core

Grounded panel

Motor

Power/communication cable
(For connecting power supply
 and host controller) *2

Connection cable *2

is a shield box.

*1  The driver is grounded by directly contacting the heat sink to the ground panel.
*2  Our cables are used.

The driver uses parts that are sensitive to electrostatic charge. Take 
measures against static electricity since static electricity may cause 
the driver to malfunction or suffer damage.

Alarm

When an alarm generates, the motor will stop. At the same time, the PWR/
ALM LED will blink in red. Before resetting an alarm, always remove the cause 
of the alarm and ensure safety.
This section describes an alarm specific to the compact driver.
If an alarm not described here generates, refer to the OPERATING MANUAL 

AZ

 Series Function Edition.

Alarm code

29h

Number of times the LED blinks

9

Alarm type

CPU peripheral circuit error

Reset using the ALM-RST input

Not possible

Motor excitation

Non-excitation *

Cause

The CPU peripheral circuit was damaged.

Remedial action

Contact your nearest Oriental Motor sales 
office.

 

* When an alarm generates, the motor current will be cut off and the motor will 

lose its holding torque. 
When an electromagnetic brake motor is used, the electromagnetic brake will 
hold a load in position.

Summary of Contents for Alpha Step AZ Series

Page 1: ...ithout observing the instructions that accompany a WARNING symbol may result in serious injury or death Handling the product without observing the instructions that accompany a CAUTION symbol may resu...

Page 2: ...on connecting a power supply whose positive terminal is grounded The connectors CN1 CN2 CN3 and CN4 of the driver are not electrically insulated When grounding the positive terminal of the power suppl...

Page 3: ...nication with the master station via RS 485 communication PWR ALM LED White Red Blue y This LED is lit in white while the main power supply is input y This LED will blink in red if an alarm protective...

Page 4: ...ing spaces between the drivers z Dimension unit mm in Mass 39 g 0 086 lb 35 1 38 41 1 61 43 1 69 49 1 93 R 1 7 5 0 0 7 2 0 08 18 5 0 73 R1 75 0 07 Connection For protection against electric shock do n...

Page 5: ...Connector housing 105308 1204 Molex Incorporated Contact 105300 2200 Molex Incorporated Designated crimping tool 63827 5600 Molex Incorporated Applicable lead wire y AWG22 to 20 0 3 to 0 5 mm2 y Oute...

Page 6: ...easures must be taken against the EMI that the motor and driver may give to adjacent control system equipment as well as the EMS of the motor and driver itself in order to prevent a serious functional...

Page 7: ...r less non condensing Altitude Up to 1 000 m 3 300 ft above sea level Surrounding atmosphere No corrosive gas dust water or oil Storage environment Shipping environment Ambient temperature 25 to 70 C...

Page 8: ...6 6018 www orientalmotor com br Please contact your nearest Oriental Motor office for further information 4 8 1Higashiueno Taito ku Tokyo 110 8536 Japan Tel 03 6744 0361 www orientalmotor co jp Tel 08...

Reviews: