![ORGA L85EX Installation And Maintenance Manual Download Page 29](http://html1.mh-extra.com/html/orga/l85ex/l85ex_installation-and-maintenance-manual_1650420029.webp)
Version 2.1
29
TROUBLESHOOTING
1.
Open the cover assembly, see section
2.
Check if the electrical connections in the
housing are tight.
•
Connection to terminal L (+).
•
Earth connection PE.
•
Connection to terminal N (-).
•
Earth connection (A) in the housing.
3.
If necessary, correct the connection(s).
4.
Switch on the mains power supply.
5.
Check if the LED’s function.
•
If yes, switch off the power supply and
close the lighting fixture.
•
If not, check the power supply from
the control panel.
6.
On the control panel, turn the mains power switch to the ON position.
7.
Check if the LED’s function.
•
If yes, switch off the power and close the lighting fixture.
•
If not, replace the control unit.
8.
Close the cover assembly, see section
.
4.3
Replace the dome
1.
Connect the live wire from the cover
assembly with terminal -.
Apply a torque of
minimum 0.75 and maximum 1.25 Nm.
2.
Connect the neutral wire with te.
Apply a torque of minimum 0.75 and
maximum 1.25 Nm.
3.
Connect the earth wire with terminal M.
Apply a torque of minimum 0.75 and
maximum 1.25 Nm.
4.
Connect the second earth wire (A) to the
earth connection (B).
5.
Close the lighting fixture. Refer to
.
N(-)
PE
L(+)
A
B
WARNING
Only use cable lugs of the eyelet type.
Note
Do not strip the insulation of the wiring more than is necessary.
+
m
-
Summary of Contents for L85EX
Page 14: ...DESCRIPTION 14 Version 2 1...
Page 22: ...INSTALLATION 22 Version 2 1...
Page 26: ...MAINTENANCE 26 Version 2 1...
Page 30: ...TROUBLESHOOTING 30 Version 2 1...
Page 59: ...Version 2 1 59 C IECEx CERTIFICATE C 1 IECEx Certificate of Conformity L85EX...
Page 60: ...60 Version 2 1...
Page 61: ...Version 2 1 61...
Page 62: ...62 Version 2 1...
Page 63: ...Version 2 1 63...
Page 64: ...64 Version 2 1...
Page 66: ...66 Version 2 1...