![Orcon HRC 300 4B P Fitting And Maintenance Instructions Download Page 8](http://html1.mh-extra.com/html/orcon/hrc-300-4b-p/hrc-300-4b-p_fitting-and-maintenance-instructions_1648408008.webp)
8
Fitting and maintenance instructions HRC 300/400 4B(P/RH)
Dipswitch settings HRC 300 4B(P/RH)
ON
1 2
ON
5 6 7 8
ON
ON
ON
ON
ON
ON
ON
ON
ON
1 2
ON
ON
ON
ON
ON
3 4
3 4
ON
ON
ON
ON
ON
1 = OFF, 2 = ON
90 m
3
/h
5 = OFF, 6 = OFF, 7 = OFF, 8 = OFF
200 m
3
/h
5 = OFF, 6 = ON, 7 = OFF, 8 = OFF
220 m
3
/h
5 = OFF, 6 = OFF, 7 = OFF, 8 = ON
230 m
3
/h
5 = OFF, 6 = ON, 7 = ON, 8 = OFF
250 m
3
/h
3 = ON, 4 = OFF
125 m
3
/h
5 = ON, 6 = OFF, 7 = OFF, 8 = ON
270 m
3
/h
5 = OFF, 6 = ON, 7 = OFF, 8 = ON
280 m
3
/h
5 = OFF, 6 = ON, 7 = ON, 8 = ON
300 m
3
/h
5 = ON, 6 = ON, 7 = OFF, 8 = ON
300 m
3
/h
1 = ON, 2 = ON
100 m
3
/h
5 = ON, 6 = OFF, 7 = OFF, 8 = OFF
210 m
3
/h
5 = OFF, 6 = OFF, 7 = ON, 8 = OFF
225 m
3
/h
5 = ON, 6 = ON, 7 = OFF, 8 = OFF
240 m
3
/h
5 = OFF, 6 = OFF, 7 = ON, 8 = ON
260 m
3
/h
3 = OFF, 4 = ON
150 m
3
/h
5 = ON, 6 = OFF, 7 = ON, 8 = OFF
275 m
3
/h
5 = ON, 6 = ON, 7 = ON, 8 = OFF
290 m
3
/h
5 = ON, 6 = OFF, 7 = ON, 8 = ON
300 m
3
/h
5 = ON, 6 = ON, 7 = ON, 8 = ON
300 m
3
/h
3 = ON, 4 = ON
175 m
3
/h
Low
High
Middle
3 4
5 6 7 8
5 6 7 8
5 6 7 8
5 6 7 8
5 6 7 8
5 6 7 8
5 6 7 8
5 6 7 8
5 6 7 8
5 6 7 8
5 6 7 8
5 6 7 8
5 6 7 8
5 6 7 8
5 6 7 8
Factory setting:
L = 100m
3
/h
M = 150m
3
/h
H = 225m
3
/h
ON
1 2 3 4 5 6 7 8