background image

n

Using the upper mark on the template, insert a No. 8 screw (included) at eye
level leaving the screw head about 1/8th inch (3mm) out from the wall. (Use
expanding anchors in plaster or masonry if necessary).

n

Slip the slotted keyhole in the back of the controller box over the extended
screw [Figure 19].

n

Push a No. 8 screw (included) through the Bottom Mounting Hole [Figure 19]
in the controller box and tighten until the box is held firmly to the wall, but
do not over-tighten.

The Controller has separate compartments for the AC line power input and the
low voltage outputs. You must keep the input power and the low voltage in their
separate places when wiring the
controller box.
The controller has a built in trans-
former that must be connected to
an AC line voltage source. Check
the back of the controller box for
power requirements. This connec-
tion should be made by a licensed
electrical contractor in accordance
with the requirements of the
National Electrical Code and other
state and local codes.

Wiring the AC input

Caution: 

do not connect the controller to one phase of a there-phase power system

used by a pump or other electrical equipment.

The controller has a nipple-mounted external power connection [Figure 21]. Use
this 1/2 inch (13mm) NPT nipple to connect the controller to a standard electri-
cal junction box that should be UL Listed (or equivalent) or comply with IEC or
EN standards (or equivalent).

n

Turn off the AC power at the AC circuit breaker and apply an appropriate
safety lockout. Verify that the power has been turned off to the installation site
using an AC voltmeter set for the correct measurement range.

n

Use power feed wire of 14 gauge (AWG) minimum with a temperature rating
of 155 degrees Fahrenheit (68 degrees Celsius) or higher.

n

Install the conduit and associated fittings. Connect the AC electrical power
wiring to the source by following all the right codes and local standards.

n

Connect the junction box (not included) to the NPT nipple [Figure 21].

n

Connect the source power conduit to the entrance of the junction box, fol-
lowing all the appropriate codes.

n

Connect the source wires to the wires extending from the controller. Take
care to follow the correct color code. For USA: connect the Green for
Ground, Black for Live, and White for Neutral. Often the source ground may
be bare copper conductor rather than green wire. For Europe: Live is Brown
and Neutral is Blue, there is no ground connection required. Be sure that all
wires are connected to the proper source wire.

n

Make sure all connections are made with code-approved insulated connec-
tors.

n

Be sure to place a weatherproof gasket and lid on the junction box.

1. Wiring the Electric Valves

n

If the distance between the controller and valves is under 700 feet (210
m), use WaterMaster

®

sprinkler wire or 20 gauge (AWG) plastic jacketed

thermostat wire to connect the controller to the valves. If the distance is
over 700 feet (210 m), use 16 gauge (AWG) wire.  Terminals accept up to
14 gauge wire. The wire can be buried in the ground; however, for more
protection wires can be pulled through conduit and buried underground.
Be careful to avoid burying the wires in locations where they could be
damaged by digging or trenching in the future.

FIGURE 22: Connecting Timer Wires to Valves

n

Each valve has two wires. One wire is to be connected as the common.
The common wires for all the valves can be connected together to one
common wire going to the timer. The other valve wire is to be connected
to the specific station wire that will control that valve 

[See Figure 22].

n

All wires should be joined together using wire nuts, solder, and/or vinyl
tape. For additional protection to waterproof connections, a WaterMaster®
grease cap can be used.

n

To avoid electrical hazards, only one valve should be connected to 
each station.

2. Connecting Valve Wires to the Timer

n

Remove the terminal compartment cover.

n

Strip 1/4" (6 mm) of the plastic insulation off the end of each wire.

n

Determine which valve you want to connect to which station. Connect 

Valves

Specific 
Zone Wire

Wire 
Connectors
in Grease Caps

Solenoids

Common 
Wires

Jacket

8

Installing Valves, Pump Start
Relays & Master  Valves

7

s e c t i o n

OPEN

'AA' SIZE BATTERY

'AA' SIZE BATTERY

1

2

3

4

5

6

7

8

9

10

11

12

PUMP COM1 COM2

1/2" (13 mm)
NPT Nipple

Junction
Box

Wire
Connectors

FIGURE 21: AC Wiring Using Junction Box

1/2" (13mm) NPT Nipple

Junction Box

Wire Connectors

WTM220330 57962-24 rG.qx  12/14/01  1:16 PM  Page 8

Summary of Contents for WaterMaster 57662

Page 1: ...l del usuario Programadores para sistemas de aspersi n Orbit Manuale d installazione Manuale d uso Programmatore per irrigazione Orbit Installationshandbuch Benutzerhandbuch Orbit Steuerger t f r Bew...

Page 2: ...ontaje exterior 28 Instalaci n de las v lvulas el encendido de la bomba y las v lvulas principales 30 Otros productos y accesorios de calidad 31 Resoluci n de problemas 32 Introduzione 33 Preparazione...

Page 3: ...recessed into the panel and must be pressed with a small pointed object such as a pen or pencil tip Notable Programming Features Two Watering Programs Summary The Timer gives you the option of using o...

Page 4: ...12 00 AM will appear in the display with three arrows pointing to the year month and day n Use the and keys to set the correct time of day When the correct time of day is reached press the ENTER key...

Page 5: ...ation 1 See Figure 6 FIGURE 6 Station Duration for Program A n You can set the watering duration from 1 to 99 minutes Press and hold the key to advance the number of minutes or use the key to go in re...

Page 6: ...he rotary dial to AUTO then press the MANUAL key The display will show AB MANUAL and ALL will be blinking See Figure 10 This indicates all stations will semi automatically water for their assigned dur...

Page 7: ...able Rain Delay Mode To stop automatic watering for 24 48 or 72 hours use the RAIN DELAY mode key n With the rotary dial set to AUTO press the RAIN DELAY key once then press ENTER The Timer will force...

Page 8: ...rew a No 8 screw through each of the two holes at the bottom of the box into the wall See Figure 16 3 Connecting the Transformer n With the wiring terminal shroud off find the two terminal holes label...

Page 9: ...Remove the rubber weather plug from the hole in the center and unscrew the one fixing screw pull the plastic cover forward to reveal the AC wiring n Use a punch to create a hole in the blind Bottom Mo...

Page 10: ...the wires extending from the controller Take care to follow the correct color code For USA connect the Green for Ground Black for Live and White for Neutral Often the source ground may be bare copper...

Page 11: ...tallation of most brands of indoor mount timers UL listed Automatic Valves Durable non corrosive plastic construction Automatic valves are available in anti siphon or straight valves with safe low vol...

Page 12: ...national models are CSA and CE approved Trademark Notice WaterMaster is registered trademark of Orbit Irrigation Products Inc The information in this manual is primarily intended for the user who wil...

Page 13: ...Orbit Irrigation Products Inc 845 North Overland Rd North Salt Lake Utah 84054 57962 24 Rev G 1 800 488 6156 1 801 299 5555 www orbitonline com WTM220330 57962 24 rG qx 12 14 01 1 17 PM Page 54...

Reviews: