background image

 

7

PROGRAMMING 

(with build-in options RS232 and Analogue output)

 

Software Version 7520_V5.hex   CS: 1120 

 

The menu will be opened with the key MENU.  With the same key the submenu will scroll 
at  the  display.  The  required  parameter  will  be  confirmed  with  ACK.    Its  value  will  be  set 
with UP or DOWN. The flashing digit - Cursor - will be positioned with ACK. The sign and 
the decimal point can be set when the flashing display is positioned outside of the display 
(no digit flashing). The decimal point will be adjusted with UP, the sign with DOWN. 
 
KEY 

DISPLAY 

FUNCTION 

 
MENU 

OrdEr 

Display resolution  

ACK 

CCCC.dd 

Select with UP, DOWN and SET from CCCCCC. to C.ddddd 

MENU 

SP1 

Set Point 1 

ACK 

001000 

Select with UP, DOWN and SET 

MENU 

SP2 

Set Point 2 

ACK 

001500 

Select with UP, DOWN and SET 

MENU 

SP3 

Set Point 3 

ACK 

002500 

Select with UP, DOWN and SET 

MENU 

SP4 

Set Point 4 

ACK 

003000 

Select with UP, DOWN and SET 

MENU 

PrESEt 

Display Offset 6 digits with Decimal Point and Sign 

ACK 

000000 

Select with UP, DOWN and SET 

MENU 

 

AOUtL   

Display value for Analogue Output 0/4mA and 0/-10V. 

ACK 

 

00000 

 

Select witht UP, DOWN and SET 

MENU 

 

AOUtH   

Display value for Analogue Output 20mA and +10V. 

ACK 

 

01000 

 

Select with UP, DOWN and SET 

MENU 

BAUD 

Baud Rate  

ACK 

19200 

Select with UP, DOWN and SET from 300 to 19200 bd. 

MENU 

 

rS Adr 

 

Address of Data Port: 0 activates RS232. One of addresses 

ACK 

 

ADDR01  

01 ... 31 activates

 

RS485 

MENU 

dEIin 

Termination sign for data output 

ACK 

nonE 

nonE, Cr, LF, CrLF, nul 

MENU 

IntEr 

Transmission Interval of the RS Port 

ACK 

nonE 

nonE, 0.1, 0.2, 0.5, 1.0, 3.0, 5.0, 10.0, Hand 

MENU 

Fn bcd  (*) 

Number of digits for conversion into RS232/485  

ACK 

POS  6 

POS 1 … POS 6   positive BCD parallel logik  (*)  

 

 

nEG 1 … nEG 6    negative BCD parallel logik  (*) 

MENU 

Fn SIG 

Activation of SIGN 

ACK 

nEG 

Selection of the SIGN control 

 

 

nEG 

“+” at Pin 25 illuminates the SIGN 

 

 

POS 

“0” at Pin 25 illuminates the SIGN 

 

 

OFF 

the SIGN is deactivated 

 

MENU 

OC7520 

Measuring Mode 

 
 
 
 
 
 
 
 

Summary of Contents for OC 7520

Page 1: ..._GBM_21312 Programmable Display for BCD parallel Data Ports OC 7520 Owner s Manual ORBIT CONTROLS AG Z rcherstrasse 137 CH 8952 Schlieren Z rich Tel 41 44 730 2753 Info orbitcontrols ch www orbitcontr...

Page 2: ...2...

Page 3: ...BEACHTEN Dieses Ger t wurde sorgf ltig verpackt Falls es bei Ihnen in besch digtem Zustand eintrifft benachrichtigen Sie unverz glich den Orbit Controls Kundendienst Tel 41 1 730 2753 oder Fax 41 1 7...

Page 4: ...of the instrument 9 5 1 Upper Terminals Supply 9 36VDC 9 5 2 Upper Terminals Supply 230VAC 9 5 3 BCD data inputs RS232 data outputs and Analogue Outputs 10 5 4 BCD parallel Inputs 10 5 5 Excitation s...

Page 5: ...d from the keyboard Analog Output is an option which permits generation of 0 4 20mA or 0 10V from the BCD parallel input data shown at the display The output of 12 bits 4096 increments can be free ass...

Page 6: ...character ANALOGUE OUTPUT 0 20mA 4 20mA max load 300 Ohm 12 bit 250V RMS Isolation 0 10V or 0 10V load 10 kOhm 12 bit SET POINTS Four free programmable Set Points SP1 SP4 activate four NPN transistors...

Page 7: ...nt 4 ACK 003000 Select with UP DOWN and SET MENU PrESEt Display Offset 6 digits with Decimal Point and Sign ACK 000000 Select with UP DOWN and SET MENU AOUtL Display value for Analogue Output 0 4mA an...

Page 8: ...T MENU SP3 Set Point 3 ACK 002500 Select with UP DOWN and SET MENU SP4 Set Point 4 ACK 003000 Select with UP DOWN and SET MENU PrESEt Display Offset free settable ACK 000000 Select with UP DOWN and SE...

Page 9: ...Upper Terminals Supply 24VDC Set Points with transistor outputs 5 2 Upper Terminals Supply 230VAC Set Points with four Relays The relay and the transistor outputs can be combined The relays can be ass...

Page 10: ...INPUT 1 800 000 2 400 000 3 200 000 4 100 000 5 80 000 6 40 000 7 20 000 8 10 000 9 8 000 10 4 000 11 2 000 12 1 000 13 800 14 400 15 200 16 100 17 80 18 40 19 20 20 10 21 8 22 4 23 2 24 1 25 SIGN 26...

Page 11: ...11 5 5 Excitation supply for external sensors...

Page 12: ...ransmitting Interval Menu step IntEr none Uninterrupted transmission 0 1 10 0 Seconds Hand Command from PC any letter from the PC keyboard any character or ENTER Number of digits Menu step Fn bcd POS...

Page 13: ...990818 Supply 230VA Mode BCD parallel Input 123456 Display 123456 7 1 Test Conditions According to Norms IEC 801 4 IEC 1000 4 4 EN 50052 1 7 2 Test Set Up 7 3 Test Results Zone 1 2kV Burst Display wi...

Reviews: