background image

MNL940-677-000  

 

 

 

REV - B   

 

 

 

3/20/2017 

 

12

 

POWERING MOTORS

 

 

Driving an AC motor presents a special problem. Most motors require a starting current that can 
be several times higher than the running current. This current may last for a few cycles to several 
seconds depending on the construction and mechanical load on the motor. This current is 
sometimes referred to as the motor’s “locked rotor” current. This current is not to be confused 
with a typical AC in-rush current that usually occurs over the course of one or less cycles of the 
AC waveform. The latter is a consequence of where in the AC cycle that a load switch closes. 

 

The model 1200's fold back current limiting can be an advantage when starting motors. During 
the starting period the motor will attempt to draw excessive power from the inverter. The fold back 
circuit will reduce the output voltage in order to maintain the maximum output current. During this 
time the current supplied to the motor will remain sinusoidal, this allows the motor to start rotating. 
Once the motor reaches its normal operating speed, it generates the required “back EMF” to 
reduce the supply current to the nominal “run” value for the motor. 

 

 

 

POWERING NON-LINEAR LOADS

 

 

Loads utilizing rectifiers and SCRs interact with the AC power source and have a significant effect 
on the distortion of the output waveform. Consider the use of a bridge rectifier followed by a 
capacitive filter, the current waveform associated with this circuit is illustrated below in figure 3-3. 
The input current to this type of circuit is drawn in large “gulps” whenever the voltage across the 
capacitor falls below the peak of the input waveform. The capacitor charging current is limited 
only by the series impedance present in the wiring and capacitor.  Because the impedance of 
large electrolytic capacitors is very small this action causes a current wave form with a peak value 
several times the RMS value. This ratio of peak current to RMS current is known as “crest factor”. 
High values of current crest factor cause distortion of the AC voltage waveform.  

  

 
The amount of distortion incurred is dependent on many factors and is beyond the scope of this 
manual. It should be noted that this type of load may cause the output waveform to exhibit “flat 
topping” This should not be associated with a defect of the inverter. Most “real world” electric 
distribution systems will exhibit similar distortion for this reason. 

 

Figure 3-3 below give an example of a non-linear load. In this case the load current is said to be 
discontinuous as it does not flow over the full cycle of the output waveforms. This action can 
cause perturbations on the output waveform. This may show up as ringing or clipping. Ringing 
can be reduced by adding a small resistive “pre-load” of about 10 to 20 watts across the output 
terminals.  

VAC IN

NON - LINEAR CIRCUIT EXAMPLE

VAC IN

V OUT DC

VOUT UNFILTERD

INPUT CURRENT

 

 

FIGURE 3-3 NON-LINEAR LOAD EXAMPLES 

 

Summary of Contents for Behlman INV-1200 Series

Page 1: ...T BEHLMAN CUSTOMER SERVICE DEPARTMENT PHONE TOLL FREE 1 800 874 6727 EMAIL SERVICE BEHLMAN COM WEB WWW BEHLMAN COM OR WRITE BEHLMAN CUSTOMER SERVICE DEPARTMENT 80 CABOT COURT HAUPPAUGE NY 11788 PHONE...

Page 2: ...the presence of flammable gases or fumes Operation of any electrical instrument in such an environment constitutes a definite safety hazard KEEP AWAY FROM LIVE CIRCUITS Operating personnel must not re...

Page 3: ...us conditions due to the exposure of hazardous voltage that can be lethal if contacted Neither Behlman Electronics Hauppauge NY USA nor any of the subsidiary sales organizations can accept any respons...

Page 4: ...be refused the customer being liable for all shipping handling and repair costs When packing for reshipment use the original shock absorbent material and shipping container to preclude damage to the...

Page 5: ...ial Authorization RMA number This number must be attached to the equipment sent back for warranty repair Equipment must be shipped back to Behlman prepaid No collect shipments will be accepted Behlman...

Page 6: ...arm Contacts 2 4 Optional Step up Transformer 3 0 OPERATING INSTRUCTIONS 3 1 Controls and Indicators 3 2 Optional Alarm Contacts 3 3 Operational Considerations Load Limitations Powering Reactive Loads...

Page 7: ...gged steel enclosure making them well suited to operation in industrial applications Available options include an AC input bypass and signaling contacts The AC bypass option is available in two config...

Page 8: ...protected Thermal Thermal cut out that monitors temperature Shuts down during over temp conditions Automatic Reset MECHANICAL WIDTH 17 in 43 2cm 19 standard EIA rack panel LENGTH 17in 48 3cm HEIGHT 3...

Page 9: ...nt the inverter by the mounting ears only If the unit is intended for use in a mobile or other high vibration application the use of additional support for the rear of the chassis is highly recommende...

Page 10: ...with respect to earth This situation does not meet the requirements of NEC section 250 regarding separately derived AC source To allow compliance with NEC rules an additional common terminal is provi...

Page 11: ...MNL940 677 000 REV B 3 20 2017 6 FIGURE 2 2 INV1200 WIRING WITH BYPASS OPTION FIGURE 2 3 INV1200 WIRING WITH BYPASS AND TB OPTIONS...

Page 12: ...t Each function provides one set of dry form C contacts which accommodates any logic required The internal relays will change state if any of the three voltages are outside of limits required to provi...

Page 13: ...standard 120VAC output to the higher value In addition the bypass option can also be included with the external transformer A block diagram of the optional transformer configurations is provided in fi...

Page 14: ...ion provides a terminal block 6 AC LINE INPUT TERMINALS Screw type terminal block provided with alarm bypass option For connection to bypass source 7 FAN EXHAUST Heated air exhaust Minimum 4 inch clea...

Page 15: ...e sound of the cooling fans should be evident 3 The appropriate front panel LEDs should be illuminated 4 To test the inverter use a True RMS type meter to confirm the output voltage is as specified 5...

Page 16: ...s the INV 1200 series to start most high in rush loads in its power range It must be understood that the DC power source suppling the inverter must also have this capability in order to derive these b...

Page 17: ...bridge rectifier followed by a capacitive filter the current waveform associated with this circuit is illustrated below in figure 3 3 The input current to this type of circuit is drawn in large gulps...

Page 18: ...at the output that contains the original sine wave information The 20 KHz carrier frequency is removed by a low pass LC filter This provides an amplified version of the original modulation signal to...

Page 19: ...in inverter Check polarity if ok the unit may have an internal fault Return for service WARNING Service of this device requires specialized equipment and trained personnel There are no internal user...

Page 20: ...MNL940 677 000 REV B 3 20 2017 15 5 0 MECHANICAL OUTLINE ALL DIMENSIONS ARE IN INCHES UNLESS OTHERWISE NOTED...

Page 21: ...EV B 3 20 2017 16 REVISION HISTORY Rev ECO DESCRIPTION DATE N A INV 1200 Gen 2 Initial Release 9 16 2016 A 17 030 Revised specification figure 2 1 to 2 3 redrawn 2 28 17 B 17 032 Corrected text figure...

Reviews: